Mounting and installation of the compact control panels
Power supply (150 W)
5
107 | 354
Building Technologies
008851_s_en_--
Fire Safety
2016-01-27
5.7.4.2 X8 output voltage
Pin
Designation
Description
10
+B
I-begr.
Connection for battery, current limited via internal battery fuse F2 (without parallel
switching)
9
+B
I-unbegr.
Connection for battery, not current limited (when switching in parallel: Fuse in the
cable tree)
8
+24 V
Supply 24 V
7
+24 V
Supply 24 V
6
+24 V
Supply 24 V
5
+24 V
Supply 24 V
4
+24 V
Supply 24 V
3
0 V
Supply output 0 V
2
0 V
Supply output 0 V
1
0 V
Supply output 0 V
Admissible cable cross-section: 0.2…2.5 mm²
Batteries may be connected either on terminal 10 or, with external fuse, to
terminal 9.