Mounting and installation of the compact control panels
Module bus cards
5
179 | 354
Building Technologies
008851_s_en_--
Fire Safety
2016-01-27
Example for pin assignment at slot 1
Connector
Pin
Designation
Description
X11
1
FIR
Horn/alarm monitored
2
FIRE_OUT_1-
3
FIR
Horn/alarm monitored
4
FIRE_OUT_2-
X12
1
FIR
Horn/alarm monitored
2
FIRE_OUT_3-
3
FIR
Horn/alarm monitored
4
FIRE_OUT_4-
X11
5
FIR
Horn/alarm monitored
6
FIRE_OUT_5-
7
FIR
Horn/alarm monitored
8
FIRE_OUT_6-
X12
5
FIR
Horn/alarm monitored
6
FIRE_OUT_7-
7
FIR
Horn/alarm monitored
8
FIRE_OUT_8-
Admissible cable cross-section: 0.14…1.5 mm
2
n = Slot no.
4
3
6
5
8
7
2
1
4
3
6
5
8
7
2
1
Xn1
Xn2
Out 1
Out 2
Out 3
Out 4
+
-
+
-
+
-
+
-
Out 5
Out 6
Out 7
Out 8
+
-
+
-
+
-
+
-