Recess sizes (W x H x D)
● Housing (Eco) 456 x 424 x 97.5 mm
● Housing (Standard) 456 x 424 x 177.5 mm
● Housing (Large Extension) 456 x 424 x 277.5 mm
● Housing (Comfort) 456 x 822 x 177.5 mm
● Housing (Large) 456 x 822 x 277.5 mm
These dimensions have been measured from the plastering or casing.
You will find information about formwork boxes in document 008843, Planning.
For fixing the station in the niche of the wall, the station must be placed on the
floor of the niche and screwed in this position.
This guarantees a simple mounting and that the base of the station and the wall
mountings are not burdened by the weight of the batteries.
1. Place the station on the niche floor and mark the holes for the dowels (only 3
pieces per station).
2. Remove the station, drill the holes for the dowels and insert the dowels.
3. Screw the hanger bolts (6.1) into the wall. Use the supplied nuts (6.7) for this
purpose and screw the hanger bolts into the wall using a spanner or ratchet.
Then remove the nuts again.
4. Now place the washer (6.2), the pressure spring (6.3) and another washer (6.4)
onto the hanger bolts (6.1) one after another.
5. Now place the rear panel (7 / 6.5) onto the hanger bolts that have been
prepared.
6. Place a washer (6.6) and hexagon nut (6.7) onto the hanger bolts one after
another. The pressure springs press the rear panel forwards, thereby allowing
for accurate depth alignment.
7. Align the housing by tightening or loosening the hexagon nuts (6.7) so that the
surface of the operating unit is level with the plaster. This is to ensure that the
FM blind is level with the wall.
8. Fix the operating unit (9) to the wall with the two bottom screws (10).
9. If available, screw down the operating add-on (5) using the two top screws (4).
10. Place the FM blind (3) onto the rear panel so that the upper bracket is placed
on the housing (7).
11. Screw down the FM blind with the four fixing screws (2).
12. Plug the plastic stoppers (1) into the four fixing screws (2).