Mounting and installation of the compact control panels
Door contact kit [DE]
5
244 | 354
Building Technologies
008851_s_en_--
Fire Safety
2016-01-27
5.36 Door contact kit [DE]
5.36.1 Installation
The door contact kit FCA2009-A1 is needed for a class 3 key depot [DE] and must
not be used for other applications. The door contact is fitted on the housing such
that it is triggered when the cover cap is removed.
Figure 130: Installing door contact kit FCA2009-A1
1 Crossed recess sheet-metal screws for fixation
2 Mounting holes in housing
3 Door contact switch
4 Pre-assembled pigtails
1. Use the two sheet-metal screws (1) to screw the door contact switch (3) in the
position shown (contact towards front) using the two holes on the housing (2).
2. Wire up the door contact with pre-assembled strands (4) in accordance with the
pin assignment on fire brigade periphery module FCI2001-D1 on FSD tamper
connection. You can also connect the door contact to a free I/O contact on the
periphery board.
3. If necessary, secure the strands to the self-adhesive mounting plate supplied
on the housing.