Mounting and installation FC2080
Installing the operating unit and operating add-on
6
310 | 354
Building Technologies
008851_s_en_--
Fire Safety
2016-01-27
Figure 171: Installing the required components, taking operating unit FCM2028-A1 as an example
1 Operating unit
2 Flange with threaded holes for securing the module
3 Connector strip X13 for network module
4 Network module (SAFEDLINK) FN2001-A1 with ES ≥ 12
5 2x fixing screw
6 PMI & mainboard FCM2027
7 Adapter for power supply (including ribbon cable)
8 Connector strip X3 peripheral data bus connection
1. Plug the network module (SAFEDLINK) (4) into connector X13 (3) of the
operating unit (1).
2. Secure the module to mounting flange (2) with both screws (5). Ensure that it is
secured correctly to avoid interrupts.
3. Plug the adapter (7) into connector X3 (8) of the PMI & mainboard (6) so
inscription 'TOP' is at the top.
1
2
3
4
5
6
7
8