Mounting and installation FC2080
Installing the key safe adapter [DE]
6
313 | 354
Building Technologies
008851_s_en_--
Fire Safety
2016-01-27
6.14 Installing the key safe adapter [DE]
The key safe adapter SDA3000 [DE] is used to connect the fire brigade key depot
[DE] to the fire control panel FC2080. The following options for controlling the key
safe adapter are available and are described using examples for the wiring:
● Via an I/O module and controlled via the FDnet
● Via an I/O module, e.g., the FDCIO222, with heating isolation
● Via I/O card (programmable) FCI2008-A1
You will find detailed information on the key safe adapter in the manufacturer's
original document 'SDA3000 installation instructions', which comes with the key
safe adapter.
6.14.1 Installation on the carrier (19", option)
Key safe adapter SDA3000 is installed as standard on a carrier (19", option). The
carrier (19", option) has 3 prepared installation positions for the key safe adapter,
each with one rectangular cable entry and 3 mounting holes.
In this type of installation, the cable duct may have to be removed and the right
half cut away to make enough space for the key safe adapter.
Figure 174: Standard installation of the key safe adapter on the carrier (19", option)
1 Carrier (19", option)
2 Additional terminal block, if required
3 I/O module FDCIO224 (example)
4 DIN rail
5 Openings for cable entry to key safe adapter (3)
6 Key safe adapter in right-hand position
1
2
3
4
5
6