Mounting and installation of the compact control panels
Periphery board (4 loops)
5
83 | 354
Building Technologies
008851_s_en_--
Fire Safety
2016-01-27
5.4.2.2 X5 monitored horn outputs 1 and 2
Pin
Designation
Description
4
SOUND2-
Horn output 2 (-)
3
Horn output 2 (+)
2
SOUND1-
Horn output 1 (-)
1
Horn output 1 (+)
Admissible cable cross-section: 0.2…1.5 mm²
5.4.2.3 X6 alarm and fault monitored outputs
Pin
Designation
Description
4
FAU_OUT
Output fault
3
VSYS_O
Supply output for consumer fault
2
AL_OUT-
Alarm output (-)
1
Alarm output (+)
Admissible cable cross-section: 0.2…1.5 mm²
1 Remote
transmission
+
-
1
2
X5
SOUND2-
F403
+
-
3
4
SOUND1-
2.3 ... 5.5 kΩ
2.3 ... 5.5 kΩ
F400