5
Operation
Switching off / Switching on
118
Building Technologies
A6V10380629_en--_a
Fire Safety
2015-09-10
6. Select the 'RT FIRE channels OFF' command.
a
The command execution display confirms successful execution of the
command by displaying
.
a
The 'RT Fire' is switched off.
a
The LED 'Remote alarm Off' on the Person Machine Interface is illuminated.
LED statuses:
l
Off
l
Steady on with isolation
l
Flashing with fault
Switch off 'RT Fire' via 'On / Off' menu item in 'Functions' menu:
w
You are logged onto at least 'Access level' 2.1.
w
You are in 'Main menu'.
1. Select the menu item 'Functions'. The menu 'Functions' is displayed.
2. Select the 'On / Off' menu item.
a
The 'Functions 'On / Off'' dialog window opens.
3. Open the filter 'Element category'.
a
The 'Element category' filter opens.
4. Select 'Alarmg.'.
a
The element category 'Alarming control group' is displayed in the filter
'Element category'.
5. Press 'Set'.
a
The element search starts.
a
All 'Alarming control groups' are displayed in the event list.
6. Highlight a 'Alarmg.'.
a
The highlighted entry is displayed with a bright background.
7. Press 'Execute commands' on the dialog window toolbar.