FTI2001-U1

Fire terminal board

Installation

Mounting

MP-UL 3.1

A6V10315040_b_en_--

Smart Infrastructure

2020-08-26

Summary of Contents for FTI2001-U1

Page 1: ...FTI2001 U1 Fire terminal board Installation Mounting MP UL 3 1 A6V10315040_b_en_ Smart Infrastructure 2020 08 26 ...

Page 2: ...xpress authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Industry Inc Smart Infrastructure 8 Fernwood Road Florham Park NJ 07932 Tel 1 973 593 2600 www usa siemens com fire Edition 2020 08 26 Document ID A6V10315040_b_en_ A5Q00050753 Siemens Industry...

Page 3: ... board FTI2001 5 1 1 Description 5 1 2 Installation 6 1 3 Views 8 1 4 Pin assignments 9 1 4 1 Wiring overview 9 1 4 2 X15 Supply output 11 1 4 3 X17 X16 Supply input 1 2 11 1 5 Indicators 11 1 6 Adjustment elements 12 1 7 Technical data 12 2 FCC Statement 13 ...

Page 4: ...4 14 A6V10315040_b_en_ ...

Page 5: ...d power supply or via the DC 24 V AUX output of the periphery board of a fire control panel or voice alarm fire control panel For uninterrupted operation the external power source requires battery backup Remote displays FT2014 or remote terminals FT2015 are supplied via the auxiliary DC output The FTI2001 has the following features Fire terminal board FTI2001 Description 1 A6V10315040_b_en_ 5 14 ...

Page 6: ... 1 A each 1 2 Installation The fire terminal board FTI2001 is for the network terminal 3 1 2 X1 X400 X3 X15 X16 X17 Figure 1 Installation of the fire terminal board FTI2001 into the network terminal 1 Holes for securing the fire terminal board on the back box 2 Fire terminal board FTI2001 3 4x fixing screw X1 No connect Fire terminal board FTI2001 Installation 1 6 14 A6V10315040_b_en_ ...

Page 7: ... the fire terminal board 2 on the back box using the four fixing screws 3 2 Use the ribbon cable supplied with the operating unit to connect operating unit to X3 3 When connecting supplies make sure no AC is applied Connect power supply to X5 Vsys input If redundancy is needed also connect power supply to X6 Vsys2 input 4 Only apply AC after wiring is complete Fire terminal board FTI2001 Installat...

Page 8: ...400 X3 X17 X16 X15 X1 X40 H206 H207 H205 H204 H203 H202 H201 S1 ON F203 F204 F202 F201 Figure 2 Printed circuit board view of fire terminal board FTI2001 Fire terminal board FTI2001 Views 1 8 14 A6V10315040_b_en_ ...

Page 9: ...sed Fuses F201 Fuse for supply output 1 F202 Fuse for supply output 2 F203 Fuse for supply input 1 Vsys1 F204 Fuse for supply input 2 Vsys2 Switch S1 Switch for supply supervision of X16 and X17 1 4 Pin assignments 1 4 1 Wiring overview The supply must be routed redundantly if the network terminal is supplied in a fail safe manner via a fire control panel or a voice alarm fire control panel Featur...

Page 10: ...y connections allowed for PS 1 PS 2 Periphery board FCI2016 FCI2017 X1001 AUX 1 2 3 4 PAD 3 AUX PAD 4 AUX UL Fire protective signaling listed regulated power supply Power supply inputs input 1 input 2 All power limited outputs are supervised in respect of input voltage Input 1 is necessary for power supply Input 2 is for redundant power supply Power supply outputs output 1 output 2 Supervised and ...

Page 11: ...3 VSYS 1 GND 2 VSYS 1 System supply DC 24 V 1 VSYS 1 System supply DC 24 V 1 5 Indicators LED Color Function Condition Meaning H201 Yellow Supply output 1 Off Fuse ok On Fuse damaged H202 Yellow Supply output 2 Off Fuse ok On Fuse damaged H203 Yellow Supervision of the voltage at the supply input 2 VSYS2 1 Off Supply available On No supply and supervision is activated S1 1 ON H204 Yellow Supervisi...

Page 12: ...2 VSYS 2 Voltage DC 24 V Operating current Max 11 mA Fuse input 1 F203 1 Amp Schurter AG P N 3404 0116 Fuse input 2 F204 1 Amp Schurter AG P N 3404 0116 Supply output Plug X15 Designation VSYS 1 VSYS 2 GND 1 GND 2 Voltage DC 24 V Curent Max 1 A per output Fuses output 1 and 2 F201 F202 1 Amp Schurter AG P N 3404 0114 Supervisory Power limited supervised for input 1 and 2 voltage Connection termina...

Page 13: ... accordance with the instructions manual may cause interference to radio communications It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area is likely to cause inte...