background image

 

D

 

GB

 

 

A5E02871132C       DS05 

Seite 1 von 4 

page  1 of 4 

 

 

 

 

GAMMA 

instabus

 

 
 

UP 204 Raum Controller Contouch 

titanweiss 

5WG1 204 2AB11 

carbonmetallic 

5WG1 204 2AB21 

aluminiummetallic 

5WG1 204 2AB31 

pianoschwarz 

5WG1 204 2AB51 

 
UP 204 Room Controller Contouch 

Titanium white 

5WG1 204 2AB11 

Carbon metallic 

5WG1 204 2AB21 

Aluminum metallic 

5WG1 204 2AB31 

Piano black 

5WG1 204 2AB51

 

 
 
 
 

Bedien  und Montageanleitung 
Operating and Mounting Instructions 

 
 
 
Stand:   März 2013 
Issued:  March 2013 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 

Produkt  und Funktionsbeschreibung 

Der  Raum  Controller  Contouch,  im  Folgenden  Contouch  ge
nannt,  vereint  die  Funktionen  eines  grafischen  Anzeigedisplays 
mit bis zu 18 Raumbedienfunktionen, eines Einzelraumtempera
turreglers mit Sollwertvorgabe und Betriebsarteneinstellung, ei
nes  Temperatursensors  und    eines  Fan Coil  Unit  Bediengerätes 
in einem Busteilnehmer. 
Der Contouch ist in  den Farbvarianten titanweiss, carbonmetal
lic, aluminiummetallic und pianoschwarz erhältlich. 
 
 
 
Für den Raum Controller Contouch ist folgendes Zubehör erhält
lich: 
 
Contouch Flash Kit 

 

5WG1 204 8AB01 

 
Dieser  Flash Kit  besteht  aus  einem  Wechseldatenträger,  einer 
microSDHC Karte,  mit  zwei  Adaptern,  einem  micro  SD  Adapter 
und einem USB microSD Leser.  
 
Die Basis des Gerätes ist ein hochwertiges 320 x 240 Pixel Farb
display  2,8“  mit  Touchscreen  und  Drehrad.  Dieses  verfügt  über 
eine Dreh / Druckfunktion. 
Bedient wird der Contouch über den Touchscreen und das Dreh
rad. Die auf dem Display angezeigten Schaltflächen können zum 
Schalten  und  Dimmen  von  Leuchten,  zur  Steuerung  des  Son
nenschutzes  oder  zum  Abrufen  und  Speichern  von  Szenen  ver
wendet werden. Die Funktionen und Zustände können mit Tex
ten und Symbolen  grafisch auf  dem Display in 4 verschiedenen 
Designs dargestellt werden. Text  und Alarmmeldungen können 
ebenfalls  zur  Anzeige  gebracht  werden.  Alarmmeldungen  wer
den  über  ein  akustisches  Signal  und  über  die  LED  Anzeige  be
sonders  hervorgehoben.  Über  den  Touchscreen  lässt  sich  die 
Anzeige  der  Texte  und  Meldungen  zwischen  bis  zu  6  Sprachen 
auswählen. 
 
Der  im  Contouch  integrierte  Raumtemperaturregler  ist  speziell 
für den Einsatz in Räumen ausgelegt, die geheizt und / oder ge
kühlt  werden  und  deren  Raumtemperaturregelung  abhängig 
von  bis  zu  vier  Raum Betriebsarten  (Komfortbetrieb,  Pre
Komfortbetrieb,  Energiesparbetrieb  und  Schutzbetrieb)  erfolgt. 
Über einen Parameter ist bei Bedarf einstellbar,  dass  der Regler 
nicht  alle  vier  Betriebsarten  berücksichtigen  soll  sondern  nur 
drei  (Komfortbetrieb,  Energiesparbetrieb  und  Schutzbetrieb) 
oder  nur  zwei  (Komfortbetrieb  und  Schutzbetrieb).  Der

 

Raum

temperaturregler

 

ist

 

als  Zweipunktregler  (Thermostat)  oder  als 

stetiger Regler (P , PI Regler) einsetzbar. 
 
Auf  dem  Display  des  Contouch  werden  die  aktuellen  Raum
Betriebsarten,  Automatik   oder  Handbetrieb,  die  Innen   bzw. 
Aussentemperatur,  die  Solltemperatur,  ein  geöffnetes  Heiz  
oder  Kühlventil,  Taupunktbetrieb  oder  geöffnete  Fenster  über
sichtlich und selbsterklärend dargestellt.   
 
Über  eine  spezielle  Anzeigeseite  werden  über  den  Touchscreen 
die  Einstellungen  zur  Raumtemperaturregelung  durchgeführt. 
Dort  kann  die  Raum Betriebsart  direkt  vor  Ort  gewählt  werden. 
Damit  ist  der  Handbetrieb  aktiv.  Im  Handbetrieb  kann  jede 
Raum Betriebsart  dauerhaft  aktiviert  und  nicht  durch  ein  Bus
Telegramm geändert werden.  
Der Regler bietet die Möglichkeit, die Dauer der Betriebsart Kom
fort  zu  verlängern.  Dazu  wird  auf  dieser  speziellen  Bedienseite  
auf dem Touchscreen die Schalt  
fläche „Komfortbetrieb Verlängerung“ betätigt und per  
Drehrad die Dauer der Komfortverlängerung eingestellt.  
Die  Einstellung  der  Soll Temperatur  erfolgt  auf  der  Anzeigeseite 
zur  Raumtemperaturregelung  direkt  in  °C/°F  bezogen  auf  die 
Raumbetriebsart Komfortbetrieb oder als relativer Wert, Verschie
bung vom Basissollwert  in K. Über das Drehrad des Reglers kann 
der  vorgegebene  Sollwert  zu  einem  höheren  oder  niedrigerem 
Wert  verschoben  werden,  wobei  der  Bereich  der  Verschiebung 
einstellbar ist. 
Die  Einstellung  Automatik  kann  ebenfalls  direkt  am  Contouch 
selektiert werden. Dann erhält der Regler seine Betriebsart über 
ein  Telegramm  vom  Bus  oder  über  das  interne  Zeitschaltpro
gramm.   
 
 
Bei  Räumen,  welche  über  eine  Fan  Coil  Unit  beheizt  und  /oder 
gekühlt werden, kann der Contouch als Bediengerät für die Lüf
tersteuerung eingesetzt werden. 
Die aktuelle Lüfterstufe wird auf dem Display angezeigt.  
Im  Handbetrieb  kann  man  die  Drehzahlstufe  des  Lüfters  über 
das Drehrad am Contouch einstellen.  
Mit der Drehzahlstufe „0“ wird  der Lüfter ausgeschaltet und ein 
ggf.  geöffnetes  Ventil  wird  geschlossen,  d.h.  der  Raum  wird 
dann  weder  geheizt  noch  gekühlt.  Wird  daraufhin  der  Sollwert 
für  den  Hitzeschutz  überschritten  bzw.  der  Sollwert  für  den 
Frostschutz  unterschritten,  wird  bei  einem  stetigen  Regler  der 
Automatikbetrieb aktiv und bei  einem Zweipunktregler  der Lüf
ter  auf  die  höchste  Lüfterstufe  eingeschaltet.  Der  Regler  heizt 
bzw.  kühlt  bis  zum  Erreichen  des  Sollwertes  der  bisher  einge
stellten Betriebsart. 
Mit der Auswahl „A“ wird über das Drehrad am Contouch die 
Lüftersteuerung auf Automatikbetrieb gesetzt. Dann erfolgt die 
Drehzahlvorgabe über die Regelung. 
 
Mit  der  Bedienung  des  Contouch  wird  die  Displaybeleuchtung 
eingeschaltet.  Nach  einer  bestimmten,  zu  parametrierenden, 
Zeit schaltet sich die Beleuchtung aus. Das Gerät ist im Standby 
Betrieb. 
 

Product and Application Description 

The  Contouch  room  controller,  hereinafter  referred  to  as  Con
touch, combines the functions of a graphic display with up to 18 
room operating functions, an individual room temperature con
troller  with  setpoint  indication  and  operating  mode  setting,  a 
temperature sensor and a fan coil unit control panel in one bus 
node. 
The  Contouch  is  available  in  the  colour  variations  titanium 
white, carbon metallic, aluminum metallic and piano black. 
 
 
 
The  following  accessories  are  available  for  the  Contouch  room 
controller: 
 
Contouch Flash Kit 

 

5WG1 204 8AB01 

 
This flash kit consists of a removable data carrier, a micro SDHC 
card with two adapters, a micro SD Adapter and a USB micro SD 
reader.  
 
The basis of the equipment is a high quality 320 x 240 pixel col
our  display  2.8"  with  touchscreen  and  rotary  control.  This  is 
equipped with a rotary/push button function. 
Contouch is operated by the touchscreen and the rotary control. 
The buttons shown on the display can be used for switching and 
dimming lights, for regulating sun protection or for the retrieval 
and  storage  of  scenes.  The  functions  and  conditions  can  be 
shown graphically with texts and symbols on the display in 4 dif
ferent designs. Text and alarm messages can  also be  displayed. 
Alarm  messages  are  specially  highlighted  by  an  acoustic  signal 
and the LED display. The touchscreen can be used to select from 
up to 6 languages for the display of texts and messages. 
 
 
 
 
The room temperature controller integrated in Contouch is spe
cially  designed  for  use  in  rooms  which  are  heated  and  /  or 
cooled where the manner of room temperature control depends 
on  up  to  four  room  operating  modes  (comfort  mode,  pre
comfort  mode,  energy saving  mode,  and  protection  mode).  As 
required, a parameter can be set so that the controller does not 
consider  all  four  operating  modes,  but  rather  only  three  (com
fort  mode,  energy saving  mode  and  protection  mode)  or  only 
two  (comfort  mode  and  protection  mode).  The

 

room  tempera

ture  controller

 

can  be  used

 

as  a  two point  controller  (thermo

stat) or a continuous controller (P or PI controller). 
 
The current room operating modes, automatic or manual opera
tion, the interior or exterior temperature, the setpoint tempera
ture,  an  open  heating  and  cooling  valve,  melting  point  opera
tion or open windows are clearly shown on the display in a self
explanatory manner.   
 
By means  of a special  display page, the room temperature con
trol  parameters  can  be  set  using  the  touchscreen.  There  the 
room operating mode can be selected directly on site. The man
ual mode is activated in this way. In manual mode, every room 
operating mode can be permanently activated and not changed 
by a bus telegram.  
The controller offers the option of extending the duration of the 
Comfort  operating  mode.  For  this  purpose,  the  "Comfort  mode 
extension" button is  pressed  on this special touchscreen  opera
tor page and the length of the Comfort mode extension set by a 
rotary control.  
The  setpoint  temperature  is  set  directly  in  °C/°F  on  the  display 
page for room temperature control based on the room operating 
mode Comfort mode or as a relative value, shifting from the base 
setpoint in K. The rotary control  of the controller can be  used to 
shift  the  specified  setpoint  to  a  higher  or  lower  value,  whereby 
the range of the offset can be adjusted. 
The automatic mode setting can also be selected directly on the 
Contouch.  The  the  controller  receives  its  operating  mode  di
rectly  by  telegram  from  the  bus  or  via  the  internal  time  switch 
program.   
 
 
 
In rooms which are heated and / or cooled by a fan coil unit, the 
Contouch can be used as a control panel for the ventilator con
trol. 
The current fan speed is shown on the display.  
In manual operation, the speed level of the fan can be set by the 
rotary control on the Contouch.  
At speed level "0", the fan switches off and a possibly open valve 
closes,  i.e.  the  room  is  then  neither  heated  nor  cooled.  If  the 
setpoint for heat protection is then exceeded or the setpoint for 
frost protection fallen short of, automatic mode becomes active 
in the case of a continuous controller and the fan is switched to 
the highest fan speed if a two point controller is used. The con
troller  heats  or  cools  until  reaching  the  setpoint  of  the  previ
ously set operating mode. 
With option "A", the Contouch rotary control is used to set the 
fan control to automatic mode. Then the speed is specified by 
the control system. 
 
 
The  display  lighting  switches  on  when  Contouch  is  operated. 
The lighting switches off after a certain time period, which must 
be configured. The device is in standby mode. 

Summary of Contents for Gamma instabus UP204 Contouch

Page 1: ...ler heizt bzw kühlt bis zum Erreichen des Sollwertes der bisher einge stellten Betriebsart Mit der Auswahl A wird über das Drehrad am Contouch die Lüftersteuerung auf Automatikbetrieb gesetzt Dann erfolgt die Drehzahlvorgabe über die Regelung Mit der Bedienung des Contouch wird die Displaybeleuchtung eingeschaltet Nach einer bestimmten zu parametrierenden Zeit schaltet sich die Beleuchtung aus Das...

Page 2: ...essbereich 0 40 C Auflösung 0 1 K Genauigkeit in Bezug zur Fühlertemperatur 1 5 K bei Referenzbedingungen 2 0 K bei Umgebungsbedingungen und im Messbereich Time programs with weekly switching plans can be configured for the 18 room operating functions and for setting the room operating mode of the controller Up to 16 switching points can be set for each time switch program The time switch programs...

Page 3: ...rgungsklemme aufstecken Die Klemmen in die Führungsnuten des Busankopplers stecken und die Klemmen bis zum Anschlag nach unten drücken Connections 6 pin plug connector for attaching and connecting with the bus coupler Mechanical specifications Casing plastic Dimensions L x W x D 116 x 86 x 14 mm without rotary push button and without plug connector guidance L x W x D 116 x 86 x 24 mm with rotary p...

Page 4: ...weise Die Bedienungsanleitung ist dem Kunden auszuhändigen Das defekte Gerät mit Busankoppler ist mit einem Rücklie ferschein der zuständigen Vertriebsniederlassung zurückzu senden Bei zusätzlichen Fragen zum Produkt wenden Sie sich bitte an unseren Technical Support Connecting the bus and supply terminals The terminals E1 are suitable for solid leads with a diameter of 0 6 0 8 mm Remove insulatio...