background image

Siemens Building Technologies

CM2N4625E / 02.1999

Landis & Staefa Division

1/10

4

625

OpenAir

TM

Air damper actuators

GIB13...1
GIB33...1

Rotary version three-position control
AC 24 V or AC 230 V

Electromotive rotary actuators for three-position control, nominal torque 35 Nm,
operating voltage AC 24 V or AC 230 V, for three-position control, span
mechanically adjustable between 0...90°, pre-wired with 0.9 m long connection
cables.
Type-specific variations with adjustable auxiliary switches for supplementary
functions and potentiometer for position indication.

To control air dampers in ventilating and air conditioning plants

• 

using a nominal torque of 35 Nm for damper surfaces up to 6 m

2

, friction-dependent

• 

Ideal with modulating three-position controllers or ON/OFF-controls (e.g., outside air
dampers, flue gas dampers, etc.)

The actuator's rotational movement (clockwise or counterclockwise) depends on the
electrical control.
As soon as the operating voltage AC 24 V or AC 230 V is applied, the actuator starts to
turn.

The connected damper can be operated as follows via the respective actuator control:

• 

Damper opens (0° 

 90°)

• 

Damper closes (90° 

 0°)

• 

Damper remains in the current position

After uninterrupted runtime of approximately 200 s, the actuator turns off in the same
direction.

The position indicator located on the shaft adapter displays the rotational angle position
of the damper blade.

To manually adjust the actuator or the air dampers, the gear train must be disengaged
using the button PUSH". Refer to "Operating and setting elements" in the chapter
"Mechanical design".

Use

Functions

Basic functions

Rotational movement

Three-position control

Fail-safe function

Position indication

Manual override

Summary of Contents for GIB131.1E

Page 1: ...rollers or ON OFF controls e g outside air dampers flue gas dampers etc The actuator s rotational movement clockwise or counterclockwise depends on the electrical control As soon as the operating voltage AC 24 V or AC 230 V is applied the actuator starts to turn The connected damper can be operated as follows via the respective actuator control Damper opens 0 90 Damper closes 90 0 Damper remains i...

Page 2: ...ious mounting options depending on the direction of rotation and shaft length separate parts such as the shaft adapter with position indicator and other mounting parts are shipped separately with the actuator The actuator comes with 0 9 m long pre wired connection cables The following accessories and spare parts are available for function upgrades of the actuators see data sheet N4699 Accessories ...

Page 3: ...pers You can manually adjust the actuator by pushing the button PUSH The actuator can be fastened to shafts with various diameters and in various shapes square round using just one screw due to the L G patented mounting Insert the shaft adapter from either side into the opening for the shaft adapter depending on the damper shaft length For short shafts the shaft adapter is on the duct side The sha...

Page 4: ...er 4 Connection cable for power supply 5 Connection cable for auxiliary switches 6 Gear train disengagement button 7 8 Adjustment dials for auxiliary switches A and B 9 Position indicator 10 Self centering shaft adapter 11 Locking ring for shaft adapter 12 Adapter for position indicator 13 Mounting bracket 4626Z23 10 11 4626Z25 9 4626Z22 11 12 10 4626Z24 9 Setting and operating elements Arrangemen...

Page 5: ... is within the required tolerance Voltage drops at the feed lines must be included Electric parallel connection of these actuators is possible only via relay if used with types GDB 3 1 GLB 3 1 SQE3 SQE8 SQR3 or SQR8 Mechanical Do not mechanically couple the actuators The quantity of actuators required depends on several torque factors After obtaining the damper torque rating Nm m2 from the manufac...

Page 6: ... the dampers and the exact switching position for switches A and B the actuator can only be adjusted with a mounted shaft adapter and position indicator in accordance with the mounting instructions If necessary you can limit the rotational angle in increments of 5 for the entire span by positioning the shaft adapter in the respective position The mounting sets which are used to change the rotation...

Page 7: ...ower consumption running actuator holding economy function AC 24 V 20 HD 384 III as per EN 60 730 EN 60 742 max 10 A 50 60 Hz 10VA 10 W 1VA 0 5 W after 200 s Power supply AC 230V for GIB331 1E GIB335 1E GIB336 1E Operating voltage Control signal AC 230 V wires 6 4 clockwise Control signal AC 230 V Wires 7 4 counter clockwise Protection class Feeder protection external Frequency Power consumption t...

Page 8: ...onditions Operation Climatic conditions Mounting location Temperature Humidity non condensing IEC 721 3 2 Class 2K2 32 70 C 95 r h Class 2M3 IEC 721 3 3 Class 3K5 inside weather protected 32 55 C 95 r h IP Code Housing type according to EN 60 529 IP 54 Conformity In accordance with the directives set forth by the European Union Electromagnetic compatibility EMC Low voltage directive 89 336 EEC 73 ...

Page 9: ...ormally open contact gray pink Q14 S4 Switch B Input black red Q21 S5 Switch B Normally closed contact black blue Q22 S6 Switch B Normally open contact black pink Q24 Positioner P1 Potentiometer 0 100 P1 P2 white red a P2 Potentiometer pick off white blue b P3 Potentiometer 100 0 P3 P2 white pink c 4626A01 Y1 G G0 SP SN AC 24 V GBB13 1 S2 S3 S5 S6 7 P3 S1 S4 Y 6 P1 P2 Y2 N AC 24 V SELV PELV N Regu...

Page 10: ...a Division min 7 300 73 85 8 m a x 9 5 900 min 100 min 60 min 200 20 10 230 4 2 67 5 3 4626M01 100 27 6 ø 5 7 15 197 max 20 P1 P3 1 7 S1 S6 Taptite M6 x 16 13 1 5 GCA 1 GBB 1 GIB 1 Ø 8 25 6 mm 6 18 mm Dimensions Dimensions in mm 1999 Siemens Building Technologies Ltd ...