Siemens Building Technologies, Inc

.                                                                                                                                                         P84391-003B 

8 Fernwood Road                                                                                                                                                                                             Sheet 2 of 4 

 Florham Park, New Jersey 07932 
 
 

Figure 1:  ULC Directional Characteristics 

81dB

83dB

-6dB

-3dB

95dB

-3dB

-6dB

85dB

-3dB

-3dB

-6dB

95dB

-6dB

20° 30°

80°

30°

27°

60°

48°

 
 
NOTES:   

1. 

The strobe will produce 1 flash per second over the Input Voltage 
range.   

2.  This horn/strobe model meets the required light distribution 

patterns defined in UL 1971 and ULC-S526-02.   

3. 

This model is UL/ULC Listed for indoor use with a temperature 
range of +32

°

F to +120

°

F (0

°

C to +49

°

C) and maximum humidity 

of 93% 

±

 2% RH.  The effect of shipping and storage 

temperatures shall not adversely affect the performance of the 
appliance when it is stored in the original cartons and not 
subjected to misuse or abuse. 

 
 
When calculating the total current:  Use Tables 3 & 3A to determine the highest value of “RMS Current” for an individual HS-MC then multiply the value 
by the total number of HS-MC Appliances.  Be sure to add the currents for any other appliances powered by the same source and to include any 
required safety factors. 
 
Note: These notification appliances are UL Listed as “Special Application”.  They are intended to be used only with Siemens notification appliance 
circuits. 
 

CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT. 
 

 

Table 3:  Current Ratings (Horn Only) 

Maximum RMS Current (Amps) 

Input Voltage 

Lo 

Med 

Hi 

DC 16-33VDC 

0.027 

0.068 

0.110 

FWR 16-33VRMS 

0.041 

0.050 

0.094 

Table 3A:  Current Ratings (Strobe Only) 

Maximum RMS Current (Amps) 

Input 

Voltage 

15cd 30cd 75cd  110cd 

DC 16-33VDC 

0.064 0.098 0.175  0.233 

FWR 

16-33VRMS 

0.108 0.164 0.268  0.368 

 

 
THESE APPLIANCES WERE TESTED TO THE VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING FILTERED DC OR UNFILTERED 
FULL-WAVE-RECTIFIED VOLTAGE.  DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.   
 
Note: Refer to the installation instructions for the appropriate NAC to find the maximum allowed voltage drop.  Use this value along with the current draw 
for the appliance to determine the allowable wire resistance.  The maximum wire resistance between strobes shall not exceed 35 ohms.  

 

 

CAUTION:

  The strobe is not designed to be used on coded systems in which the applied voltage is cycled on and off.   

NOTE:

  The horn circuit is compatible with coded systems only if the unit is wired for independent horn and strobe operation per figure 4.  

 

 

WARNING:  MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S 

PRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS 
OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED.  OVERLOADING POWER SOURCES OR EXCEEDING FUSE 
RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN 
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for HS-MC Series

Page 1: ...strobe when connected to a notification appliance circuit running the Siemens sync protocol HS appliances can be field set for High HI medium MED dBA or low LO dBA sound output NOTE The Code 3 temporal pattern 1 2 second on 1 2 second off 1 2 second on 1 2 second off 1 2 second on 1 1 2 off and repeat is specified by ANSI and NFPA 72 for standard emergency evacuation signaling The Code 3 Horn shou...

Page 2: ...m RMS Current Amps Input Voltage Lo Med Hi DC 16 33VDC 0 027 0 068 0 110 FWR 16 33VRMS 0 041 0 050 0 094 Table 3A Current Ratings Strobe Only Maximum RMS Current Amps Input Voltage 15cd 30cd 75cd 110cd DC 16 33VDC 0 064 0 098 0 175 0 233 FWR 16 33VRMS 0 108 0 164 0 268 0 368 THESE APPLIANCES WERE TESTED TO THE VOLTAGE LIMITS OF 16 0 33 0 VOLTS FOR 24V MODELS USING FILTERED DC OR UNFILTERED FULL WA...

Page 3: ... HS MC audible is connected to a coded system the continuous horn setting must be used WIRING AND MOUNTING INFORMATION Figure 4 Audible signal and strobe operate independently Figure 4A Audible and strobe operate in unison Shunt wires are supplied STR AUD TB1 FROM FACP OR PRECEDINGAPPLIANCE TO NEXTAPPLIANCE OR EOLR FROM FIRE ALARM CONTROL PANEL FACP OR PRECEDINGAPPLIANCE TO NEXTAPPLIANCE OR END OF...

Page 4: ...C to the backbox verifying that it is seated and aligned correctly 7 Fasten the HS MC to the backbox using the supplied screws The HS MC 110cd setting is Listed for use in sleeping or non sleeping areas when installed in accordance with appropriate NFPA Standards and the AHJ WARNING A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON S FIELD OF VIEW UNDER CERTAIN CIRCUMSTAN...

Reviews: