SOUND OUTPUT (SPL) AND CANDELA SETTINGS: 
 

Figure 2:  Showing Location of Candela Selector and Jumper Plugs 

R

+   STR   -

J3

+   AUD   -

T B 1

3

J2

C

O

E

D

J1

H

L

M

B

P83511  ( )

AH

C1

R5

TOP

75

30

15

110

CANDELA SELECTOR

CANDELA 

POINTER

3

J2

C

O

E

D

J1

H

L

M

 

Factory setting is on 15 candela, Medium dB and Code 3. 

WARNING:  THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION.  

WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE.  AFTER CHANGING THE 
CANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION. 
 

Figure 3:  Jumper Plug Settings for High, Medium, Low dB, 

Code 3 Horn (or March Time)  and Continuous Horn Setting. 

J1

HIGH

LOW

H

C
O
D
E
3

3

E

D

O

C

SETTING

HORN

SETTING

HORN

J1

J2

J2

J2

M

L

H

M

L

H

M

L

MEDIUM

SETTING

HORN

CODE 3

SETTING

HORN

CONTINUOUS

SETTING

* HORN

 

• 

Use needle nose pliers to pull and properly insert the jumper 
plug.

 

• 

No jumper plug is needed for continuous horn setting.  
However, it is recommended that the jumper plug be retained 
in the unit for future use (if needed) as shown in Figure 3.

 

• 

The HS-MC must be set for Code 3 (or March Time)  horn 
when used with the sync module.  If the HS-MC audible is 
connected to a coded system,  the continuous horn setting 
must be used.

 

 
WIRING AND MOUNTING INFORMATION: 
 

Figure 4:  Audible signal and strobe operate independently. 

Figure 4A:  Audible  and strobe operate in unison.  Shunt wires are 

supplied. 

+   STR    -

+   AUD    -

TB1

+

FROM FACP OR

PRECEDING APPLIANCE

TO NEXT APPLIANCE

OR EOLR.

FROM FIRE ALARM

CONTROL PANEL (FACP) OR

PRECEDING APPLIANCE

TO NEXT APPLIANCE

OR END OF LINE

RESISTOR (EOLR).

-

-

+

+

-

-

+

    

 Figure 5: 

+   STR    -

+   AUD    -

TB1

+

TO NEXT APPLIANCE

OR EOLR

FROM FACP  OR

PRECEDING APPLIANCE

-

RED SHUNT WIRE

BLACK SHUNT WIRE

-

+

 

 

 

• 

HS-MC Appliances have in-out wiring terminals that accepts two #12 to #18 American Wire Gauge (AWG) wires at each 
screw terminal.  Strip leads 3/8” inches for connection to screw terminals. 

• 

Break all in-out wire runs on supervised circuit supervision as shown in Figure 5.  The polarity shown in the wiring 
diagrams is for the operation of the appliances.  The polarity is reversed by the FACP during supervision. 

 

The following figures (A-D) show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option.  If these 
limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the 
product.  Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed 
multiconductor cable or 3/4" conduit fittings are used. 
 

Summary of Contents for HS-MC Series

Page 1: ...strobe when connected to a notification appliance circuit running the Siemens sync protocol HS appliances can be field set for High HI medium MED dBA or low LO dBA sound output NOTE The Code 3 temporal pattern 1 2 second on 1 2 second off 1 2 second on 1 2 second off 1 2 second on 1 1 2 off and repeat is specified by ANSI and NFPA 72 for standard emergency evacuation signaling The Code 3 Horn shou...

Page 2: ...m RMS Current Amps Input Voltage Lo Med Hi DC 16 33VDC 0 027 0 068 0 110 FWR 16 33VRMS 0 041 0 050 0 094 Table 3A Current Ratings Strobe Only Maximum RMS Current Amps Input Voltage 15cd 30cd 75cd 110cd DC 16 33VDC 0 064 0 098 0 175 0 233 FWR 16 33VRMS 0 108 0 164 0 268 0 368 THESE APPLIANCES WERE TESTED TO THE VOLTAGE LIMITS OF 16 0 33 0 VOLTS FOR 24V MODELS USING FILTERED DC OR UNFILTERED FULL WA...

Page 3: ... HS MC audible is connected to a coded system the continuous horn setting must be used WIRING AND MOUNTING INFORMATION Figure 4 Audible signal and strobe operate independently Figure 4A Audible and strobe operate in unison Shunt wires are supplied STR AUD TB1 FROM FACP OR PRECEDINGAPPLIANCE TO NEXTAPPLIANCE OR EOLR FROM FIRE ALARM CONTROL PANEL FACP OR PRECEDINGAPPLIANCE TO NEXTAPPLIANCE OR END OF...

Page 4: ...C to the backbox verifying that it is seated and aligned correctly 7 Fasten the HS MC to the backbox using the supplied screws The HS MC 110cd setting is Listed for use in sleeping or non sleeping areas when installed in accordance with appropriate NFPA Standards and the AHJ WARNING A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON S FIELD OF VIEW UNDER CERTAIN CIRCUMSTAN...