Operating
7.7 Volume
HydroRanger 200 HMI
110
Operating Instructions, 06/2018, A5E36281317-AC
7.7.2
Vessel shape and dimensions
The device can be configured to suit many common vessel or tank shapes [See Vessel
shape (2.7.2.) (Page 186)]. Whenever possible, use one of those pre-defined selections.
Each shape uses the Empty distance [Empty (2.2.4.)] (Page 170)in its calculations of
volume.
Some tank shapes also require extra dimensions to calculate the volumes. Do not estimate
these values as they must be exact to ensure the accuracy of your volume calculations.
①
A
To configure volume for a tank with a half-sphere bottom, set the following:
Parameter
Index Mode/Value
Description
(Page 186)
1
Half Sphere Bottom
Selects the correct tank shape
(Page 188)
1
100
Sets maximum volume at 100 (per-
cent)
(Page 188)
1
1.3
Sets A to 1.3 m
Note
•
The default reading changes to a range from 0 to 100 [the value in Maximum Volume
•
Empty [Empty (2.2.4.) (Page 170)] is still measured to the bottom of the tank, not the top
of A.