Operating
7.8 Alarms
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
113
7.8
Alarms
7.8.1
Level
The level alarm is the most common. Use this alarm to warn you when the process is in
danger of being upset due to high or low levels. Generally, the four alarms used are Hi, Hi-
Hi, Lo, and Lo-Lo.
Set the common parameters
Prerequisite:
You must know the details of your application and substitute the values for the sample
values provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Parameter
Index
1
Value
Description
(Page 163)
Global
*Level
Operation = *Level
(Page 165)
Global
Liquid
Material = *Liquid
(Page 174)
Global
Medium
Maximum Process Speed = *Medium (1.0
m/min)
(Page 164)
Global
XPS-10
Transducer = XPS-10 (single-point preset)
Units (2.1.1.) (Page 162) Global
Meters
Units = Meters
(Page 170)
Global
1.8
Empty = 1.8 m
Span (2.2.2.) (Page 169) Global
1.4
Span = 1.4 m
1
This example assumes a base, single measurement unit. If your unit has optional dual-
point software installed, then some parameters are indexed by two level points.