Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
202
Operating Instructions, 06/2018, A5E36281317-AC
Relay Fail-safe is available only for the relay functions listed in the table below. Preset
options depend on the relay functions selected.
Relay function (2.8.1.4.)
Preset (Relay fail-safe 2.8.2.3.)
Level alarm
OFF
In-bounds alarm
Out-of-bounds alarm
Rate of Change alarm
Temperature alarm
Fixed Duty Assist, Fixed Duty Backup, Alternate
Duty Assist, Alternate Duty Backup, Service Ratio
Duty Assist, Service Ratio Duty Backup, First In
First Out: all pump controls
De-energize
Relay interval setpoint (2.8.2.4.)
Sets the length of time, in hours, between starts.
Index
Relay
Values
Range: 0 ... 9000 hours
Preset: 0.000 hours
Altered by
Preset applications (2.8.1.3.) (Page 194)
Related