Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
235
Echo lock (2.11.5.4.)
Selects the measurement verification process.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Lock OFF
Maximum verification
*Material agitator
Total lock
Related
•
Fill rate/minute (2.3.2.) (Page 173)
•
Empty rate/minute (2.3.3.) (Page 173)
•
Algorithm (2.11.2.2.) (Page 222)
•
Measurement verification (2.11.5.) (Page 233)
•
Echo lock window (2.11.5.5.) (Page 235)
If a material agitator (mixer) is used in the vessel monitored, set Echo Lock for Maximum
verification or Material agitator to avoid agitator blade detection. Ensure the agitator is
always ON while the device is monitoring the vessel to avoid stationary blade detection.
When set for Maximum verification or Material agitator, a new measurement outside of the
Echo Lock Window (2.11.5.5.) (Page 235) must meet the Measurement Verification (2.11.5.)
(Page 233) criterion.
For, Echo Lock Window (2.11.5.5.) (Page 235) is preset to zero (0). The device continuously
searches for the best echo according to the Algorithm (2.11.2.2.) (Page 222) chosen. If the
selected echo is within the window, the window is then centered about the echo. If not, the
window widens with each successive shot until the selected echo is within the window. The
window then returns to its normal width.
When Echo Lock is OFF, the device responds immediately to a new measurement as
restricted by the Fill Rate/minute (2.3.2.) (Page 173) and Empty Rate/minute (2.3.3.)
(Page 173); however, measurement reliability is affected.
Echo lock window (2.11.5.5.)
Adjusts the size of the Echo Lock Window.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Preset: 0.000
Response rate (2.3.4.) (Page 174)
Related
•
Units (2.1.1.) (Page 162)
•
Echo lock (2.11.5.4.) (Page 235)