Parameter reference
8.7 Maintenance and Diagnostics (3.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
263
Echo strength (3.2.11.4.)
Displays the strength (
in dB above 1 μV RMS) of the echo which was selected as the
measurement echo.
Index
Transducer
Values
Range: 0 ... 99 (Read only)
Noise average (3.2.11.5.)
Displays the average ambient noise (in dB above 1 μV RMS) of a noise profile after each
measurement.
The noise level is a combination of transient acoustic noise and electrical noise (induced into
the transducer cable or receiving circuitry). For more information, see Noise problems
(Page 286).
Noise peak (3.2.11.6.)
Displays the peak ambient noise (in dB above 1
μV RMS) of a noise profile after each
measurement.
Echo time filtered (3.2.11.7.)
Displays the time, in ms, from the transmission of the pulse, to when it is processed.
Index
Transducer
Values
Range: 0.0 ... 9999 milliseconds (Read only)
Related
Echo time raw (3.2.11.8.) (Page 263)
Echo time raw (3.2.11.8.)
Displays the time, in ms, from the transmit pulse to the processed echo.
Index
Transducer
Values
Range: 0.0 ... 9999 milliseconds (Read only)
Related
Echo time filtered (3.2.11.7.) (Page 263)
8.7.2.12
SmartLinx diagnostics (3.2.12.)
Note
These parameters are used to test and debug the SmartLinx card (if installed). Disregard
these parameters if you do not have a SmartLinx card installed.