Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
77
Flow exponent
(Primary Measuring Device (Page 240) = Exponential devices (Page 240))
The exponent for the flow calculation formula.
Values
Range: -999.000 ... 9999.000
Default: 1.550
Flowrate units
(Primary Measuring Device (Page 240) = Rectangular Flume BS-3680 (Page 240) or Thin
Plate V-Notch Weir BS-3680 (Page 240))
The units used for flow calculations.
Note
Shown only when 2.13.2. Primary Measuring Device (Page 240)= Rectangular Flume BS-
36806 or Thin Plate V-Notch Weir BS-36807.
Index
Single-point model
Dual-point model
Global
Transducer
Options
Ratiometric
Primary Measuring Device
*Ratiometric calculation
Absolute
Primary Measuring Device
Rectangular Flume
BS-3680 or Thin Plate V-
Notch Weir BS-3680 only)
L/S (Liters/second)
M
3
/H (Cubic meters/hour)
M
3
/D (Cubic meters/day)
FT
3
/S (Cubic feet/second)
IMPGAL/MIN (Gallons/minute – Imperial)
MIMPGAL/D (Million gallons/day – Imperial)
GAL/MIN (Gallons/minute – U.S.)
MUSGAL/D (Million gallons/day – U.S.)
V-notch angle
(Primary Measuring Device (Page 240) = Thin Plate V-Notch Weir BS-3680 (Page 240))
The V-Notch angle used in the flow calculation formula.
Values
Range: 25.000 ... 95.000
Default: 25.000
Use this parameter if the Primary Measuring Device is directly supported. The dimensions
required for each PMD vary.