Operating
7.8 Alarms
HydroRanger 200 HMI
116
Operating Instructions, 06/2018, A5E36281317-AC
7.8.6
Temperature
Use the temperature alarm to activate an alarm when the temperature reaches the ON
setpoint (2.8.1.5.) (Page 197). This alarm uses the same setpoint parameters as the level
alarms [ON Setpoint (2.8.1.5.) (Page 197) and OFF Setpoint (2.8.1.6.) (Page 197) ]
You can set a high alarm (ON Setpoint > OFF Setpoint) or a low alarm (ON Setpoint < OFF
Setpoint).
This shows a high alarm:
Parameter
Index Mode/Value Description
(Page 195)
5
Temperature Alarm on temperature
(Page 197)
5
45
ON setpoint at 45 °C
(Page 197)
5
43
OFF setpoint at 43 °C
(Page 194)
5
Transducer 1 Take the temperature reading from Trans-
ducer 1
The temperature source can be the temperature sensor built into the transducer or an
external TS-3, as set by Temperature Source (2.11.1.4.). (Page 219)
7.8.7
Loss of Echo (LOE)
Activates an alarm when the device loss of echo timer passes without detecting a valid echo.
Parameter
Index
Mode/Value
Description
(Page 194)
5
Transducer 1
Alarm on LOE for Transducer 1
(Page 195)
5
LOE
Alarm on LOE
(Page 177)
Global
0.5
Trip alarm when 0.5 minutes (30 seconds)
pass without detecting a valid echo.