Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
181
8.6.5.3
Current output function (2.5.3.)
Alters the mA output/measurement relationship.
Index
mA output
Options
mA function
Sensor mode (2.1.3.)
OFF
Level
Level, differential, or average
Space
Space
*Distance
Distance
Volume
Level or space
Flow
OCM
Head
Volume Rate
mA Input
Related
•
mA output allocation (2.5.4.) (Page 181)
•
Milliamp output (2.5.9.) (Page 182)
Altered by
Sensor mode (2.1.3.) (Page 163)
8.6.5.4
mA output allocation (2.5.4.)
Sets the input source from which the mA output is calculated.
Index
mA Output
Options
*Point 1
Point 2
Average of readings from Point 1 and Point 2
Point 3
Related
Current output function (2.5.3.) (Page 181)
Enter the point number the mA output is based on. This value depends on whether Current
Output Function (2.5.3.) (Page 181) is set as transducer or mA input.
For a single-point device, if Current Output Function (2.5.3) (Page 181) uses a transducer,
parameter mA Output Allocation (2.5.4) can only be altered if Sensor Mode (2.1.3.)
(Page 163) is set for DPD or DPA.
Parameter mA Output Allocation (2.5.4.) can be set to a particular point or range of points.
When set to a range of points, the mA output will be the average of the readings from all in
service transducers in the range. Out-of-service transducers will be ignored.