Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
198
Operating Instructions, 06/2018, A5E36281317-AC
Pump by rate (2.8.1.8.)
Sets the pump relays to accept control by rate of level change once the first ON setpoint is
reached.
Index
Single-point model
Dual-point model
Transducer
Level
Options
*OFF (pump by level)
ON
Related
•
Span (2.2.2.) (Page 169)
•
Relay function (2.8.1.4.) (Page 195)
•
Delay Between Starts (2.8.2.8.1.) (Page 207)
•
Rate (2.3.) (Page 172)
Use this function when multiple pumps are to be controlled by rate of level change rather
than by setpoints.
The delay between pump starts is set by Delay Between Starts (2.8.2.8.1.) (Page 207).
This only applies to any relays set to pump control [RelayFunction (2.8.1.4.) (Page 195) =
Fixed Duty Assist, Fixed Duty Backup, Alternate Duty Assist, Alternate Duty Backup, Service
Ratio Duty Assist, Service Ratio Duty Backup, or First In First Out].
Note
•
All pump control relay ON and OFF setpoints must be the same value.
•
If the level is within 5% of Span (2.2.2.) (Page 169) of the OFF setpoint, the next pump is
not started.
Filling indicator (2.8.1.9.)
Sets the fill rate required to activate the local display filling indicator
Index
Single-point model
Dual-point model
Transducer
Level
Values
Range: 0.000 ... 99.00 m (or equivalent, depending on units)
Response rate (2.3.4.) (Page 174)
Related
•
Units (2.1.1.) (Page 162)
•
Span (2.2.2.) (Page 169)
•
Fill rate/minute (2.3.2.) (Page 173)
This value [in Units (2.1.1.) (Page 162) per minute] is automatically set to 1/10 of Fill
Rate/minute (2.3.2.) (Page 173).