Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
201
Relay selector (2.8.2.1.)
Sets the relay index for all parameters applicable to this sub-menu.
Pump group (2.8.2.2.)
Organizes pumps into groups, for multiple pump rotations on one transducer.
Index
Relay
Options
*Group 1
Group 2
Alters
Relay Function (2.8.1.4.) (Page 195), when Relay Function (2.8.1.4.) (Page 195)
= Alternate Duty Assist or Alternate Duty Backup
Note
All relay ON/OFF points must be referenced from Empty (2.2.4.) (Page 170) (bottom of the
vessel), regardless of Sensor Mode (2.1.3.) (Page 163) selection.
Relay fail-safe (2.8.2.3.)
Sets how individual relays react to a fail-safe condition, to allow for more flexible
programming.
Index
Relay
Options
OFF
Response governed by Material level (2.4.5.) (Page 178)
Hold
Last known relay state retention.
Energize
To have the relay energize immediately on fail-safe.
De-energize
To have the relay de-energize immediately on fail-safe.
Altered by
Material level (2.4.5.) (Page 178)
Related
•
LOE timer (2.4.2.) (Page 177)
•
Relay function (2.8.1.4.) (Page 195)
Use this for operations independent of the Material Level (2.4.5.) (Page 178).