Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
205
Pump run-on (2.8.2.7.)
Run-ON Interval (2.8.2.7.1.)
Sets the number of hours between pump Run-ON occurrences.
Index
Global
Values
Range: 0.000 ... 1000
Preset: 0.000
Related
•
Run-ON Duration (2.8.2.7.3.) (Page 206)
•
Delay Between Starts (2.8.2.8.1.) (Page 207)
•
Power Resumption Delay (2.8.2.8.2.) (Page 207)
•
Level setpoint variation (2.8.2.6.2.) (Page 204)
To clear sediment in a pump-down wet well, run the pump after the normal OFF setpoint is
reached to force some solid material through. This parameter sets the time between such
events. Only the last pump running can run-ON.
Relay selector (2.8.2.7.2.)
Sets the relay index for all parameters applicable to this sub-menu.