Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
209
Override time delay (2.9.1.4.)
Defines the time used to calm (debounce) the override condition input.
Index
Transducer
Values
Range: 0.0 ... 9999
Preset: 5 seconds
Related
•
Discrete input number (2.9.1.2.) (Page 208)
•
Level override value (2.9.1.3.) (Page 208)
•
Discrete input 1 (2.9.2.1.) (Page 209)
Note
Activation of the Level Override is subject to the measurement cycle. This can add up to four
seconds to the overall response time depending on operating conditions and programming.
8.6.9.2
Discrete Input Logic (2.9.2.)
Discrete input 1 (2.9.2.1.)
Changes the behavior of Discrete Input 1.
Options
Forced OFF
Forced ON
* Normally Open
Normally Closed
Discrete input 2 (2.9.2.2.)
Changes the behavior of the Discrete Input 2.
Options
Forced OFF
Forced ON
* Normally Open
Normally Closed