Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
211
8.6.10.3
Multiplier (2.10.1.2.)
Use this feature if the remote totalizer (the device connected to the relay set to Relay
Function (2.8.1.4.) (Page 195) = Totalizer) updates too slowly or rapidly.
Index
Single-point model
Dual-point model
Global
Transducer
Options
0.001
0.01
0.1
*1
10
100
1,000
10,000
100,000
1,000,000
10,000,000
Related
•
Sensor mode (2.1.3.) (Page 163)
•
Relay function (2.8.1.4.) (Page 195)
•
Relay interval setpoint (2.8.2.4.) (Page 202)
•
Relay duration (2.10.1.3.) (Page 211)
This parameter is relevant only if Operation is set to OCM or Pumped Volume [Sensor Mode
(2.1.3.) (Page 163) = Flow rate in open channel or Pump Totalizer].
The relays on the device have a maximum frequency of 2.5 Hz. Enter the factor (powers of
10 only) by which actual volume is divided, prior to Remote Totalizer count increment.
Example: For a Remote Totalizer update by 1000s of volume units, enter 3.
8.6.10.4
Relay duration (2.10.1.3.)
Use this feature (if desired) to adjust the minimum contact closure duration of a relay set as
a totalizer or flow sampler [Relay Function (2.8.1.4.) (Page 195) = Totalizer or Flow
Sampler].
Index
Global
Values
Range: 0.1 ... 1024 seconds
Preset: 0.188 seconds
Related
Relay function (2.8.1.4.) (Page 195)
Enter minimum contact closure duration (in seconds) required by the device connected.