Parameter reference
8.7 Maintenance and Diagnostics (3.)
HydroRanger 200 HMI
254
Operating Instructions, 06/2018, A5E36281317-AC
8.7.2.2
Echo profile (3.2.2.)
Allows you to request the current echo profile either locally via the local push buttons, or
remotely via SIMATIC PDM.
To request a profile via the local push buttons:
1.
In PROGRAM mode, navigate to MAIN MENU > DIAGNOSTICS > ECHO PROFILE
2.
Press RIGHT arrow to request a profile.
Note
An Echo Profile (3.2.2.) cannot be requested when:
•
Sensor Mode (2.1.3.) (Page 163) is out of service, or when
•
Transducer (2.1.5.) (Page 164) is set to NO TRANSDUCER.
In either case, the local push button will not operate.
For more detail, see Requesting an echo profile (Page 86).
For more detail on how to request an echo profile, see Echo processing (Page 302).
8.7.2.3
Master reset (3.2.3.)
Resets all parameters to original values, with the exception of the AFES, TVT shaping, and
all relative identification parameters (Tag, Description, etc.).
Index
Single-point model
Dual-point model
Global
Transducer
Global
*Do nothing
Factory defaults
Use this feature prior to initial programming if arbitrary parameter values were used during a
bench test, or after upgrading the software. Following a Master Reset, complete
reprogramming is required.
When the factory default option is selected, the display will pause while reset is processed.
When the display returns to the Diagnostics menu, the Master Reset is complete.
CAUTION
Master Reset
Be careful when using this feature. All data for all points will be reset. For convenience, be
sure to record the values you want to re-enter.