Parameter reference
8.7 Maintenance and Diagnostics (3.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
255
8.7.2.4
Power-ON resets (3.2.4.)
Displays the number of times power has been applied since Manufacture Date (3.1.9.)
(Page 253).
Index
Global
Values
Range: 1 ... 9999 (Read only)
Related
•
Manufacture date (3.1.9.) (Page 253)
•
Power-ON time (3.2.5.) (Page 255)
8.7.2.5
Power-ON time (3.2.5.)
Displays the number of days this device has been in operation.
Index
Global
Values
Range: 1 ... 9999 (Read only)
Related
•
Manufacture date (3.1.9.) (Page 253)
•
Power-ON resets (3.2.4.) (Page 255)
The RUN Time value is updated once a day, and cannot be reset. However, in the event of a
power interruption, the counter won’t advance. Therefore, a unit that is powered down on a
regular basis will not have an accurate value.
8.7.2.6
Relay selector (3.2.6.)
Sets the relay index for all parameters applicable to this sub-menu.
8.7.2.7
Relay logic test (3.2.7.)
Forces the relay control logic into an activated or de-activated state.
Index
Relay
Options
*OFF
Activate relay control
De-activate relay control
Related
•
Relay function (2.8.1.4.) (Page 195)
This parameter tests site wiring and control logic programming. Forcing the relay to an
activated or de-activated state is similar to the device detecting an event and responding to
it. Helpful in testing new installations and diagnosing control problems.
8.7.2.8
Measurement values (3.2.8.)
Level selector (3.2.8.1.)
Sets the Level Point index for all parameters applicable to this sub-menu.
Summary of Contents for HydroRanger 200 HMI
Page 2: ......
Page 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Page 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Page 362: ......
Page 403: ......