Parameter reference
8.7 Maintenance and Diagnostics (3.)
HydroRanger 200 HMI
256
Operating Instructions, 06/2018, A5E36281317-AC
Reading (3.2.8.2.)
Corresponds to the final reading after all programming is applied.
Index
Level
Values
Range: -999 ... 9999
In general, this means that: Reading (3.2.8.2.) = [Reading x Convert Reading (2.12.5.)
(Page 238)] + Offset Reading (2.12.6.) (Page 238).
Reading measurements by operation:
Sensor mode
Vessel shape=0
Vessel shape≠0
OFF
----
----
Level
Level (3.2.8.3.) (Page 256)
Head (3.2.8.13.) (Page 258)
Space
Space (3.2.8.11.) (Page 258)
100% minus Head (3.2.8.13.)
(Page 258)
Distance
(Page 256)
(Page 256)
Difference
Level (3.2.8.3.) (Page 256)
Level (3.2.8.3.) (Page 256)
Average
Level (3.2.8.3.) (Page 256)
Level (3.2.8.3.) (Page 256)
OCM
Flow (3.2.8.14.) (Page 259)
Flow (3.2.8.14.) (Page 259)
Pump totalizer
Head (3.2.8.13.) (Page 258)
Level (3.2.8.3.)
Shows the distance in Units (2.1.1.) (Page 162) between Empty (2.2.4.) (Page 170) and the
monitored surface.
Index
Level
Values
Range: -999 ... 9999
Related
•
Units (2.1.1.) (Page 162)
•
Empty (2.2.4.) (Page 170)
•
Span (2.2.2.) (Page 169)
Distance % (3.2.8.4.)
Shows the distance between the surface and the transducer face (displays only as % of
Empty).
Index
Level
Values
Range: 0.000 ... 9999% (Displays as % of Empty; Read only)
Related
•
Units (2.1.1.) (Page 162)
•
Empty (2.2.4.) (Page 170)
Use Distance (3.2.8.12.) (Page 258) unless the distance information is required in percent.