Communications
C.13 Product ID (R40,064)
HydroRanger 200 HMI
330
Operating Instructions, 06/2018, A5E36281317-AC
C.13
Product ID (R40,064)
Product ID identifies the Siemens device type. The product ID for this device is 32.
C.14
Point data (R41,010 – R41,031)
Level Point data contain the current instrument readings. These are the values shown for the
reading measurement for each Level Point. The reading is based on the setting for Sensor
Mode (2.1.3.) (Page 163), which can be set to Level, Distance, OCM Flow, or Volume.
The measurement registers are 41,010 to 41,012. The device uses 41,010 when configured
with a single transducer and 41,010 to 41,012 when configured with two transducers [Relay
Function (2.8.1.4.) (Page 195) = Rate of Change or Temperature only]. Two transducers can
create three readings because they can generate an average or differential reading
(R41,012) as well as the two level readings (R41,010 and R41,011).
Available registers
Data
Registers
Parameter
Reading
41,010 to 41,012
Reading (3.2.8.2.) (Page 256)
Volume
41,020, 41,021
Head (3.2.8.13.) (Page 258)
Temperature
41,030 and 41,031
Transducer Temperature (3.2.8.17.) (Page 259)
The reading is expressed as a percentage of full scale, multiplied by 100:
Reading
Value
0
0.00 %
5000
50.00 %
7564
75.64 %
20 000
200.00 %
C.15
Totalizer (R41,040 – R41,043)
The totalizers are stored as 32-bit integers using two registers. The totalizers can be read
with R41,040 and R41,041 as totalizer for Point 1, and R41,042 and R41,043 as totalizer for
Point 2. The totalizer values can be reset to any value by writing that value to the registers.
The values can be cleared by writing zero (0) to the registers.