I-T-E Pressure Wire Connectors
General
NOTE: This instruction outlines the recommended installation
procedure for all MD and ND Frame pressure wire
connectors.
A.
Move breaker handle to OFF position, or depress PUSH
TO TRIP button. Breaker must be in OFF or TRIPPED
position before continuing.
B.
Remove terminal shield (1) (Figure 2) (two #6-32 screws.)
C.
Mount breaker securely. See circuit breaker instructions
for proper installation procedures.
D.
Mount pressure wire connectors (2) to terminal pads (3)
with mounting screws (4) (Figure 1). Recommended
torque is 228 in. Ib.
NOTE: Steps C and D may be completed in any convenient
order.
E.
Attach power cables to connectors and tighten set
screws (5) (Figure 1) to specifications per Table 1.
NOTE: Cables must extend straight for at least 4 inches from
face of connector to clear shield.
F
Mount removable terminal shield (6) (Figure 2) to end of
circuit breaker. Shield should be flush with end of circuit
breaker.
G.
Re-assemble terminal shield.
NOTE: When terminal cover is properly installed, wire con-
nector shield should be held securely.
NOTE: End barrier NDTS is supplied with kits 2 TA4P8500,
3TA4P8500, 2TA3P8750, 3TA3P8750, 2TA2K8750,
3TA2K8750. Barrier can be purchased as a separate
item for use with other terminal connectors.
Figure 1
Figure 2
Summary of Contents for I-T-E Sensitrip MD Series
Page 2: ......
Page 6: ...4 I T E Sensitrip Digital Circuit Breaker MD and ND Frame Outline Drawings 1 3 Pole ...
Page 8: ...6 MD and ND Frame Trip Adjustments ...
Page 12: ...10 MD and ND Frame Time Current Curve 600 1000A With Short Time Delay Set on Fixed Time ...
Page 13: ...MD and ND Frame Time Current Curve 11 1200A With Short Time Delay Set on Fixed Time ...
Page 14: ...12 MD and ND Frame Time Current Curve 600 100A With Short Time Delay Set on I2 t ...
Page 15: ...MD and ND Frame Time Current Curve 13 1200A With Short Time Delay Set on I2 t ...
Page 16: ...14 MD and ND Frame Time Current Curve 600 100A Without Short Time Settings ...
Page 17: ...MD and ND Frame Time Current Curve 15 1200A Without Short Time Settings ...
Page 18: ...16 MD and ND Frame Time Current Curve Ground Fault Trip Data ...
Page 19: ...MD and ND Frame Time Current Curve 17 Example ...
Page 20: ...18 MD and ND Frame Let Thru Curves ...
Page 31: ...Installation Diagrams 29 ...
Page 35: ...I T E Mechanical Interlock M15404 33 Figure 7 ...
Page 41: ...Installation Diagrams 39 ...
Page 49: ...Installation Diagrams 47 ...
Page 50: ...48 I T E Panelboard Connecting Straps 1 ...
Page 53: ...Installation Diagrams 51 ...