To Set the ICP-B6 Module Address:
1. Plug the programming cable of the DPU or
FPI-32 Programmer/Tester (SensorLINK)
into the two-pin receptacle on the ICP-B6.
(See Figure 2 for location only.)
2. Set the system address for the ICP-B6 by
following the instructions in the FPI-32
(SensorLINK) Programmer/Tester Manual,
P/N 315-090077, or the DPU User's
Manual, P/N 315-033260, as applicable.
Remove all system power before installa-
tion, first battery and then AC. (To power
up, connect the AC first, then the battery.)
All wiring must comply with
national and local codes.
The ICP-B6 should be installed in a UL
listed electrical box. (See Figure 10.)
Analog Loop
The ICP-B6 communicates with the MXL
through its analog addressable loops. These
loops are on either the MMB or on the op-
tional ALD-2I module of the MOM-4. They
may be wired for Class A (Style 6) or Class B
(Style 4). Figure 1 shows both wiring types
and the connections to either the MMB or to
the MOM-4 when the ALD-2I module is used.
The table on the following page lists the
maximum output currents allowed.
Installation Instructions
MODEL ICP-B6
Intelligent Control Point
The Model ICP-B6 Intelligent Control Point from
Siemens Industry, Inc. can be used as an
independent, remotely located telephone zone, a
speaker zone (25V or 70.7V RMS), or notification
appliance circuit (NAC), depending on how it is
configured. It communicates through the analog
loop of the MXL/MXLV System.
OPERATION
Up to 12 ICP-B6s can connect to each analog
loop of the MXL/MXLV. These modules must
be connected to the first 12 address locations
on the analog loop.
The 24 VDC power input for each ICP-B6
comes from either the MMB, the PSR, or from
an auxiliary power supply which is power
limited and UL listed for fire protective signal-
ing use and is rated between 24 and 27.3
VDC. Each ICP-B6 can be assigned a 32-
character, custom alphanumeric message.
Each module uses one address on either the
analog loop of the ALD-2I module or the analog
loop of the MMB board. (See Figure 1) The
ICP-B6 is programmable for different usages.
For additional information on the MXL/MXLV
System, refer to the MXL/MXLVManual, P/N
315-092036.
Addressing and Testing
Use the DPU Device Programming Unit or the
FPI-32 Programmer/Tester (SensorLINK) to
program and test the module.
NOTE:
With FPI-32 Rev. 1.3 software, only
1=MXL mode should be used when
programming a device.
P/N 315-095306-10
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada