3
Figure 2
ICP-B6 Used as a Strobe Module
+
+
+
+
+
+
-
-
-
-
-
-
POWER
LIMITED
STYLE Y
STYLE Z
15K, 1/2W, 5% EOL RESISTOR
P/N 140-820400
15K, 1/2W, 5%
EOL RESISTOR
P/N 140-820400
SUPERVISED STROBE ACTIVATION - SPECIAL APPLICATION
SUPV: 9VDC, .5mA
ACTIVATED: 16-32V UNFILTERED FULL WAVE RECTIFIED, 1.5A MAX
POLARITY SHOWN IN SUPV. CONDITION
ICP-B6 MODULE IS USED FOR
NAC SUPERVISION AND ACTIVATION
NOTES:
1. ALL WIRING MUST COMPLY WITH NATIONAL AND LOCAL CODES.
2. POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT <5K OHMS FOR TERMINALS 3-6.
3. FOR SYNCHRONIZATION OF NOTIFICATION APPLIANCES USE EITHER DSC, DSC-W, OR PAD-3.
ICP-B6 MODULE IS USED FOR
NAC SUPERVISION AND ACTIVATION
16-32 VDC
NAC UNITS
SEE TABLE 1
DC INPUT RATED
24 - 27.3 VDC FWR
SUPV:
12mA
ACTIVATED: 1.5A MAX
24-27.3 VDC, 18mA MAX
9 VDC, 0.5mA
SPECIAL APPLICATION
16-32V UNFILTERED FULL WAVE RECTIFIED
1.5A, POWER LIMITED
+
+ -
-
ICP-B6
ICP-B6
PROGRAM
PLUG
PROGRAM
PLUG
TB2
TB1
TB1
6
6
6
5
5
5
4
4
4
3
3
3
2
2
2
1
1
1
+
+
+
+
-
-
-
-
ANALOG
LOOP
CONNECTION
SUPERVISED
MODULE INPUT SUPPLY
FROM PS-35, PSR-1, OR
UL LISTED POWER SUPPLY
MANUFACTURED BY
ALARM-SAF (Model BN4-002-UL)
ELECTRICAL:
INPUT DC SUPPLY:
SUPERVISORY OUTPUT:
ACTIVATED:
JP2
JP2
JP1
JP1
EARTH
SHIELD
+
+ -
-
TB2
6
5
4
3
2
1
EARTH
SHIELD
Figure 1
Analog Loop Connections
100 OHMS MAX
ANALOG LOOP CONNECTION
(T-TAPPING ALLOWED)
OPERATES IN FULL CONFORMANCE WITH STYLE 4 (CLASS B)
*JUMPERS CAN BE REMOVED FROM MMB-3 WITH CSGM CONFIGURATION
*
*
TB1
TB1
TB1
ICP-B6
ICP-B6
ICP-B6
1
2
1
2
1
2
ALD-2I
ALD-2I
MOM-4
TB2
MOM-4
TB1
MMB
TB2
MMB
TB3
LOOP 1
LOOP 2
LOOP 1
LOOP 2
LOOP 1
LOOP 2
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
4
3
2
1
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
4
3
2
1
LOOP RESISTANCE 100 OHMS MAX
18 AWG MINIMUM WIRE
NO EOL DEVICE REQUIRED
SUPERVISED, POWER LIMITED PER NEC 760
ALL WIRING MUST CONFORM TO NATIONAL AND
LOCAL ELECTRICAL CODES