14.1.1 Setting expansion module's DIP switches
The expansion module is fitted with DIP switches. These are used to set the communication address for
communication with the processing unit.
Switches 1, 2, 3, 4, and 5 are configurable and are used to set the slave addresses, while switch 6 is used for
termination.
For the last expansion module that is used, switch 6 must be set to ON.
With one
expansion module
(standard IQHeat
50, 100, 110)
With two expansion modules
(first and then second, IQHeat120)
14.1.2 LEDs for BSP and BUS diagnostics
The expansion module has two LEDs, BSP and BUS, for diagnostics. The LEDs can light with three different
colours: yellow, green and red.
Status of the LEDs:
Mode
Status LED BUS
Communication error
Red LED lights
Communication OK
Green LED lights
Communication OK but one or more
parameters are not configured
properly
Green and red LED (yellow) lights
Mode
Status LED BSP
Incorrect BSP or slave address
Red LED flashes at 2 Hz
BSP in operation (DDC application)
Green LED lights