background image

NOTES for Figure 3:
1. All wiring must comply with national and local codes.

2. In order to provide adequate protection, it is recommended

that you do not install more than 20 devices on a single LIM-1.

3. Minimum wire gauge is 18 AWG.

4. The total wire resistance (both wires) between LIM-1s

cannot exceed 10 ohms.

5. Do not install more than 12 LIM-1s per loop.

6. All circuits are supervised.

7. Refer to the MXL/MXLV Manual, P/N 315-092036, the MLC

Installation Instructions, Document ID A6V10328217, or the
DLC Installation Instructions, Document ID A6V10239107,
for the list of compatible devices.

8. All terminals are power limited.

ANALOG LOOP

IN

+

-

IN

+

OUT

+

+

+

-

OUT EARTH

IN

+

-

IN

+

OUT

+

+

+

OUT

-

EARTH

IN

+

-

IN

OUT

+

+

+

+

OUT

-

EARTH

NOTE: WHEN USING THE

LIM-1 WITH THE DLC, 

THE FOLLOWING 

POLARITY MUST BE

OBSERVED AT THE LIM-1.

DLC LINE 1 = +

DLC LINE 2 = -

Figure 3

LIM-1 Wiring Diagram

Class B Installation

The LIM-1 may be used in two circuit configurations.

Class B (See Figure 3)

In Class B wiring each LIM-1 isolates a branch on the
circuit. Note that a short on the main branch causes
the entire loop to fail. To prevent this, mount the
LIM-1s at the MXL or FireFinder-XLS enclosure and
run each branch independently.

TO ANALOG

LOOP RETURN

INSIDE ENCLOSURE

TO ANALOG
LOOP FEED

IN

IN OUT OUT

IN

+

+

+

+

+

+

+

+

+

+

+

+

- -

+

+

-

-

-

-

-

-

-

-

-

-

-

-

IN

OUT

OUT

EARTH

EARTH

IN

IN

OUT

OUT

EARTH

IN

IN

OUT

OUT

EARTH

IN

IN OUT OUT EARTH

IN

IN OUT OUT EARTH

+

- -

+

+

-

-

+

+ -

-

+

+

-

-

+

NOTE: WHEN USING THE LIM-1 WITH THE 
DLC, THE FOLLOWING POLARITY MUST BE 

OBSERVED AT 

 THE LIM-1.

DLC LINE 1 = +

DLC LINE 2 = -

Figure 4

LIM-1 Wiring Diagram

Class A Installation (Single Loop)

Class A Single Loop (See Figure 4)

In Class A wiring the LIM-1s are wired in series with
the loop wiring. This results in a single continuous
loop. If any group in the loop has a short, that group is
lost and a Class A circuit failure results. The MXL or
FireFinder-XLS displays communication errors for the
devices and a Class A failure for the loop itself.

NOTES for Figure 4:

1. All wiring must comply with national and local codes.

2. In order to provide adequate protection, it is recommended

that you do not install more than 20 devices on a single LIM-1.

3. Minimum wire gauge is 18 AWG.

4. The total wire resistance (both wires) between LIM-1s

cannot exceed 10 ohms.

5. Do not install more than 12 LIM-1s per loop.

6. All circuits are supervised.

7. Refer to the MXL/MXLV Manual, P/N 315-092036, the MLC

Installation Instructions, Document ID A6V10328217, or the
DLC Installation Instructions, Document ID A6V10239107,
for the list of compatible devices.

8. All terminals are power limited.

P/N  315-049552-6

Document ID A6V10239166

Reviews: