95/116
Smart Infrastructure
Basic Documentation LME7...
CC1P7105en
14 Error code list with operation via external AZL2 display
24.07.2020
Error code
Clear text
Possible cause
Loc: 225
PWM fan faulty
- After the prepurge speed was reached, the
minimum PWM prepurge speed was undercut
(parameter 675.00) or ...
- After reaching the ignition load speed, the
maximum ignition load PWM (parameter 675.01)
was exceeded
Loc: 226
PWM fan faulty
Parameterization error:
- Speed low-fire > speed high-fire, or
- Low-fire = 0 rpm, or
- Maximum speed = 0 rpm
Loc: 227
PWM fan faulty
One or several parameters violate the minimum /
maximum limit
rSt Er1
Error in compatibility between PME7 and
LME7 during restore process
Program sequence of PME7 does not match the
LME7
rSt Er2
Error in compatibility between PME7 and
LME7 during restore process
LME7 hardware does not match the PME7
rSt Er3
Error during restore process
PME7
faulty
PME7 removed during restore process
bAC Er3
Error in compatibility between PME7 and
LME7 during backup process
Program sequence of PME7 does not match the
LME7
Err PrC
Error in PME7
Data content of the PME7 defective
No PME7 plugged in