15/61
Building Technologies
Basic Documentation LMO39…
CC1P7154en
4 Type summary (other types on request)
15.03.2018
4 Type summary
(other types on request)
The product nos. given below applies to the LMO39… burner control without plug-in base and without flame detector. For ordering information on plug-in bases and other
accessories, see Ordering.
Article no.
Type
Times in seconds
tw
max.
s
TSA
(P267)
max.
s
t1
(P265)
min.
s
t3
(P266)
min.
s
t3n
(P295)
approx.
s
t4
(P270)
approx.
s
t8
(P274)
min.
s
tow
(P296)
approx.
s
BPZ:LMO39.100C1 LMO39.100C1
Requirement
2.5
5
0
30
4,5
5
0
600
BPZ:LMO39.100C2 LMO39.100C2
Requirement
2.5
5
0
30
4,5
5
0
600
Setting range
Min.
---
0
0
0 + 5.6
0
0
0
0
Max.
---
14.994
1237
1237 + 5.6
14.994
1237
1237
1237
Increment (s)
---
0.147
4.851
4.851
0.147
4.851
4.851
4.851
Factory setting
---
4.557
0
29.106 + 5.6
4.410
4.851
0
596.673
Function parameter
Parameter number
Factory setting
Repetition limit value loss of flame or no flame at the end of safety time
0 = none
1 = none
2 = 1 x repetition
3 = 2 x repetition
4 = 3 x repetition
280
1