3/16
Building Technologies Division
CC1N7138en
18.05.2016
Technical data
Mains voltage
AC 230 V +10 % / -15 %
Mains frequency
50...60 Hz ±6 %
External primary fuse (Si)
6.3 A (slow)
Power consumption
12 VA
Perm. mounting position
Optional
Weight
Approx. 200 g
Safety class
I
(burner control with plug-in base)
Degree of protection
IP40 (to be ensured through mounting)
Perm. cable lengths
- from terminal 7 to «R»
Max. 3 m at a line capacitance of 100 pF/m
Max. 20 m at 100 pF/m
Detector cable laid separately
Max. 10 m
Remote reset laid separately
Max. 20 m
Perm. amperage at cos
0.6
LMO64...
Terminal 1
Max. 5 A
Terminals 3 and 8
Max. 3 A
Terminals 4, 5, 6 and 10
Max. 1 A
Storage
DIN EN 60721-3-1
Climatic conditions
Class 1K3
Mechanical conditions
Class 1M2
Temperature range
-20...+60 °C
Humidity
<95 % r.h.
Transport
DIN EN 60721-3-2
Climatic conditions
Class 2K2
Mechanical conditions
Class 2M2
Temperature range
-20...+60 °C
Humidity
<95 % r.h.
Operation
DIN EN 60721-3-3
Climatic conditions
Class 3K3
Mechanical conditions
Class 3M3
Temperature range
-5...+60 °C
Humidity
<95 % r.h.
Installation altitude
Max. 2,000 m above sea level
Attention!
Condensation, formation of ice and ingress of water are not permitted!
If not observed, the safety functions are no longer ensured and there will be a
risk of electric shock.
General unit data
Environmental