Technical
Instructions
LMV
Series
Document
No.
LV5
‐
1000
Section
4
Page
16
SCC
Inc.
3.
Ensure
burner
switch
is
off.
If
the
LMV5
is
not
yet
powered,
turn
on
the
power
to
the
LMV5.
4.
At
this
point,
all
safety
interlocks
that
can
be
checked
should
be
checked
in
a
safe
manner.
This
includes
but
is
not
limited
to:
low
water
cut
offs,
high
temperature
switches,
high
gas
pressure
switch,
low
gas
pressure
switch,
proof
of
closure
(POC),
etc.
5.
Later
in
the
procedure
when
the
burner
is
running,
the
rest
of
the
safety
interlocks
must
be
checked
in
a
safe
manner.
This
includes
but
is
not
limited
to:
Air
pressure
switches,
high
steam
pressure
limits,
draft
switches,
etc.
6.
Set
parameter
ProgramStop
to
Interval
1,
Phase
44.
This
will
stop
the
burner
from
progressing
past
lighting
the
pilot.
This
parameter
can
be
found
under
the
following
menu
path:
Params
&
Display
>
RatioControl
>
ProgramStop
7.
Turn
on
the
burner
switch.
The
burner
should
drive
to
pre
‐
purge
(Phase
24),
drive
to
ignition
(Phase
38),
light
the
pilot,
and
stop
in
pilot
stabilization
(Phase
44).
If
the
pilot
does
not
light
on
a
new
installation,
there
could
be
air
in
the
gas
line.
Bleed
the
air
in
a
safe
manner
if
necessary
and
attempt
to
re
‐
light
the
pilot.
8.
Once
the
pilot
is
lit,
tune
the
pilot
by
adjusting
the
ignition
position
of
the
air
actuator
and
/
or
adjusting
the
pilot
gas
pressure
regulator,
if
necessary.
Pilot
flame
should
be
stable
and
return
a
flame
signal
of
85%
or
greater.
Ignition
positions
can
be
adjusted
at
this
time
using
the
following
menu
path:
Params
&
Display
>
RatioControl
>
GasSettings
>
SpecialPositions
>
IgnitionPos
9.
Once
a
satisfactory
pilot
flame
is
established,
set
ProgramStop
to
Interval
2,
Phase
52.
The
burner
should
open
the
main
fuel
(gas)
valves
and
attempt
to
light
the
main
flame.
The
LMV5
should
show
a
flame
failure
since
the
manual
main
fuel
(gas)
valve
is
closed.
10.
If
a
flame
failure
does
occur,
proceed
to
reset
the
LMV5
and
open
the
manual
main
fuel
(gas)
valve.
The
burner
should
once
again
proceed
through
the
startup
sequence,
light
the
pilot
and
then
attempt
to
light
the
main
flame.
11.
If
the
main
flame
lights,
adjust
the
ignition
position
of
the
gas
valve
to
achieve
a
safe
main
flame.
At
this
time,
a
calibrated
stack
gas
analyzer
should
be
inserted
into
the
stack
and
used
to
evaluate
combustion.
If
the
main
flame
fails
to
light,
the
ignition
position
of
the
firing
rate
control
valve
and
/
or
the
gas
pressure
regulator
may
need
to
be
adjusted
to
achieve
a
combustible
mixture
at
the
ignition
position.
After
the
combustion
has
been
verified
to
be
safe
with
an
analyzer,
ProgramStop
can
be
left
at
Interval
2,
Phase
52
for
boil
out
or
boiler
warming
if
required.
HOME
Summary of Contents for LMV 5 Series
Page 2: ...Intentionally Left Blank ...
Page 41: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 7 Section 2 HOME ...
Page 42: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 8 SCC Inc HOME ...
Page 43: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 9 Section 2 HOME ...
Page 44: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 10 SCC Inc HOME ...
Page 45: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 11 Section 2 HOME ...
Page 46: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 12 SCC Inc HOME ...
Page 47: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 13 Section 2 HOME ...
Page 48: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 14 SCC Inc HOME ...
Page 49: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 15 Section 2 HOME ...
Page 50: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 16 SCC Inc HOME ...
Page 51: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 17 Section 2 HOME ...
Page 52: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 18 SCC Inc HOME ...
Page 53: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 19 Section 2 HOME ...
Page 54: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 20 SCC Inc HOME ...
Page 55: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 21 Section 2 HOME ...
Page 373: ...Intentionally Left Blank ...