Error
Code
Diag.
Code
Device
Display
Meaning for the LMV5x System
Corrective Action
50
Short-circuit
Pt100 Sensor
Short-circuit sensor PT100, terminals X60.1, X60.4
51
Open-circuit
Pt100 Sensor
Open-circuit sensor PT100, terminals X60.1, X60.4
52
Open-circuit Pt
100 Sensor (Line
Compens)
Open-circuit compensation line of sensor PT100, terminals
X60.2, X60.4
53
Short-circuit
Pt1000 Sensor
Short-circuit sensor PT1000, terminals X60.3, X60.4
54
Open-circuit
Pt1000 Sensor
Open-circuit sensor PT1000, terminals X60.3, X60.4
55
Short-circuit
Ni1000 Sensor
Short-circuit sensor Ni1000, terminals X60.3, X60.4
56
Open-circuit
Ni1000 Sensor
Open-circuit sensor Ni1000, terminals X60.3, X60.4
57
Overvoltage at
Input 2
Overvoltage at input 2, terminal X61
58
Open-circuit /
Short-circuit
at Input 2
Open-circuit / short-circuit input 2, terminal X61
59
Overvoltage at
Input 3
Overvoltage at input 3, terminal X62
5A
Open-circuit /
Short-circuit
at Input 3
Open-circuit / short-circuit input 3, terminal X62
5B
Output Value for
Analog Output not
available
Selected output value for analog output is not available in the
current configuration
Ensure parameter
OutValueSelection
is a valid
selection based on the devices connected to the basic
unit.
5C
Sensor already in
use (LC, FGR, or
temp. of the
combustion air)
An invalid selection was made concerning the configuration of
a temperature sensor.
Ensure the following five temperature sensor
configuration parameters have valid selections based
on the devices connected to the basic unit:
Sensor
Select
,
FGR-sensor
,
SupAirTempSens
,
AirTempX60PT1000
, and
FlueGasTempSens
.
1) Check signals wired to X62. Check wiring. Check
parameter
Ext Inp X62 U/I
. Re-wire if necessary.
Fault with Sensors Connected to Internal Load Controller, in Base Unit (LMV5)
A6
LMV5
Load
Controller
Module
1) Check pressure sensors wired to X61. Check wiring
and sensor. Check parameters
Sensor Select
and
Ext
Inp X61 U/I
. Re-wire or replace sensors if necessary.
2) If using a 4-20 mA pressure sensor, this fault occurs
when the boiler pulls a vacuum. Replace with a 0-10
Vdc sensor, or a higher range 4-20mA sensor.
Check temperature sensors connected to X60
terminals. Check wiring and sensor. Check parameter
Sensor Select.
Re-wire or replace sensors if
necessary.
Section 7
Page 45
SCC Inc.
HOME
HOME
Summary of Contents for LMV 5 Series
Page 2: ...Intentionally Left Blank ...
Page 41: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 7 Section 2 HOME ...
Page 42: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 8 SCC Inc HOME ...
Page 43: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 9 Section 2 HOME ...
Page 44: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 10 SCC Inc HOME ...
Page 45: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 11 Section 2 HOME ...
Page 46: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 12 SCC Inc HOME ...
Page 47: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 13 Section 2 HOME ...
Page 48: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 14 SCC Inc HOME ...
Page 49: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 15 Section 2 HOME ...
Page 50: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 16 SCC Inc HOME ...
Page 51: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 17 Section 2 HOME ...
Page 52: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 18 SCC Inc HOME ...
Page 53: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 19 Section 2 HOME ...
Page 54: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 20 SCC Inc HOME ...
Page 55: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 21 Section 2 HOME ...
Page 373: ...Intentionally Left Blank ...