13/39
Smart Infrastructure
LMV6 Installation Guide
CC1J7560en
3 Description of the terminals
4/21/2020
3.1.4 Terminal X71 / X72 / X73
X73
X72
X71
1 2 3 4
1 2 3 4
1 2 3
X7
1 X
72
X7
3/
011
9
Figure 7: Description of terminal X71 / X72 / X73
Terminal Coding
Type
(ASN)
Pin
Input
Output
Function
Electrical limit value
Parameter
X71
03K48
1
●
---
---
---
---
2
---
●
---
---
3
●
---
---
---
X72
04K01
1
---
●
Fan
230 V~ +10% / -15%
50 Hz
Imax 2 A
1102
2
---
●
---
---
3
---
●
---
---
4
---
●
---
---
X73
04K42
1
●
---
Load controller ON/OFF
230 V~ +10% / -15%
50 Hz
1701
1702
1705
1740
1750
2
●
---
Load controller CLOSED
230 V~ +10% / -15%
50 Hz
3
●
---
Load controller OPEN
230 V~ +10% / -15%
50 Hz
4
●
---
Flue gas recirculation (FGR), thermostat
contact
230 V~ +10% / -15%
50 Hz