Installation Instructions

1.

  For installation as a main breaker (250A and lower 

panels  only).

    Lock  off  all  power  supplying  this 

equipment before working on it. To install this kit as a 

main breaker, remove the deadfront and main lugs if 

installed. Place the main breaker connector assembly 

(Item 2) so that the ends of the assembly with the half 

holes are positioned under the section or main bus.  

Fasten  to  the  main  bus  using  the  1/4-20  hex  head 

SEMS assembly machine screws (Item 8) provided.  

Take care to see that the half hole engages the anti-

turn tab on the underside of the section bus.  DO NOT 

TIGHTEN AT THIS TIME.

2.  Attach  the  breaker  support  (Item  1)  and  the  BQCH 

support barrier (Item 10) to the base rail using (2) of 

the #10-32 slotted hex washer head thread forming 

screws (Item 6) provided as shown on page 2.

3.  Position the breaker on the breaker support (Item 1) 

and  attach  to  the  connector  assembly  using  the 

#10-32  slotted  hex  head  SEMS  assembly  machine 

screws (Item 7) provided.

4.  Torque all connections to the values specified on the 

installation and maintenance instruction label affixed 

to the rear of the deadfront.

5.  Attach the main or branch cables to the breaker and 

torque  connections  to  the  values  specified  on  the 

device,  or  if  no  values  are  specified  on  the  device, 

refer  to  the  installation  and  maintenace  instructions 

affixed to the rear of the deadfront of the panel.

6.  Remove  the  insert  plate  installed  in  any  deadfront 

opening in the area that will cover this kit.  If there is 

no  opening,  follow  the  instructions  on  page  4  to 

remove the main/ subfeed knockout.  Install the cover 

plate (Item 3) provided with this kit into the front of the 

dead front as shown by inserting two plate edge tabs 

into  one  edge  of  the  cutout  and  then  snapping  the 

other two tabs in place.  For main breaker applica-

tions,  apply  the  "MAIN"  label  (Item  4)  to  the  cover 

plate (Item 3) as shown.

7.  On 4 wire systems the neutral lug (Item 5) is required.  

The neutral lug assembly comes in the kit ready to 

assemble on the upper right or the lower left position 

of the neutral bus (Note Neutral positions shown on 

the instructional drawing).  If it is desirable to place 

the lug at the other corners of the panel, the lug may 

be disassembled and the lug pad flipped 180 degrees 

and re-assembled.  See instructional drawing below.  

Follow the torque values specified on the installation 

and maintenance label.  The lug may be attached to 

the  neutral  cross  bar  at  any  open  corner  using  the 

#10-24 slotted hex head thread forming screws (Item 

9) provided.  Again, follow the torque values specified 

on the installation and maintenance label. 

The following instructions are for the installation of a Siemens main/subfeed breaker kit for BDQ breakers in S1, S2, and P1 

Type panelboards.  The kit may be installed as a main or a subfeed in panels rated 250 amps or less.  Above 250 amps it 

may be installed in subfeed applications only. The parts provided in this kit are for connection to a 3 phase 3 or 4 wire 

system.  The breaker is not included with this kit and must be purchased separately.  Be sure to choose the appropriate 

breaker for the system in use.  For 3 wire systems, disregard the neutral connection.

12-A-1011-01 Rev. 5

-3-

-2-

DANGER

Hazardous voltage.

Will cause death or

serious injury.

Keep out.

Qualified personnel only.

Disconnect and lock off all

power before working on 

this equipment.

8.  Before energizing the panel, ensure that all connec-

tions  have  been  torqued  and  that  the  deadfront  is 

installed.

9. 

Installation as a subfeed breaker.

  Follow steps (1) 

through (8) except that any subfeed breakers or feed 

thru  lugs  assemblies  existing  in  the  panel  are 

removed.  In addition, do not install the "MAIN" label.

10.  In panels rated higher than 250A, kits mount only at 

the end of the interior designated for subfeeds.  See 

reference drawing below.  Kit connectors fasten to the 

end  holes  in  the  panel  phase  bus,  the  breaker 

support fastens to the two base rail holes nearest the 

deadfront  support,  and  the  neutral  lug,  if  installed, 

fastens to the diagonal hole pattern on the neutral lug 

pad.

NEUTRAL LUG DETAIL

400A P1 PANELBOARD INTERIOR

MAIN

END

SUB-FEED

END

Neutral cross bar

Neutral lug position

Neutral lug position

Base rail

Deadfront support

Neutral lug position

Neutral lug position

3

4

7

2

5

9

6

8

1

10

  ITEM  DESCRIPTION 

QTY

  1 

BREAKER SUPPORT 

1

  2 

BREAKER CONNECTOR ASSEMBLY 

1

  3 

COVER PLATE 

1

  4 

MAIN LABEL 

1

  5 

NEUTRAL LUG ASSEMBLY 

1

  6 

#10-32 SLOTTED HEX WASHER HEAD THREAD FORMING SCREW 

2

  7 

#10-32 HEX HEAD SEMS ASSEMBLY MACHINE SCREW* 

2

  8 

1/4-20 X 1/2 HEX HEAD SEMS ASSEMBLY MACHINE SCREW* 

3

  9 

#10-24 X 7/16 SLOTTED HEX WASHER THREAD FORMING SCREW 

3

  10 

BQCH SUPPORT BARRIER S2 

1

* SEMS ASSEMBLY SCREWS HAVE A 

CAPTIVE WASHER ON THE SCREW.