'LDJQRVWLFVXVLQJDODUPQXPEHU
DODUPVDQGIDXOWV
If alarms and faults occur on the PROFIBUS communication link, corresponding
alarm numbers are displayed on the converter (BOP/AOP).
$ODUPV
Table 7-2
Alarm displays on converter
$ODUP
QXPEHU
0HDQLQJ
A700
Cause:
The parameter or configuring settings by the PROFIBUS master are
invalid.
Remedy: Correct the PROFIBUS configuration
A702
Cause: The link to the PROFIBUS is interrupted.
Remedy: Check connector, cable and PROFIBUS master
A703
Cause:
No setpoints, or invalid setpoints (control word = 0) are being
received from the PROFIBUS master
Remedy: Check setpoints from the PROFIBUS master. Switch SIMATIC CPU
to "RUN".
A704
Cause: At least one configured internode transmitter is not yet active, or has
failed.
Remedy: Activate internode transmitter.
A705
Cause: No actual values received from converter.
Remedy: None (fault is in converter)
A706
Cause: PROFIBUS-DP communication board: Software error.
Remedy: None (fault on the PROFIBUS-DP communication board, for details
see diagnostic parameter)
A710
Cause: Converter has detected failure of communication link to PROFIBUS-
DP communication board
Remedy: None (communication board may need to be replaced)
A711
Cause: Invalid value of a CB?? parameter.
Remedy: Check P0918 (PROFIBUS address) and P2041 (communication
board parameters)
)DXOWV
Table 7-3
Fault displays on converter
$ODUP
QXPEHU
0HDQLQJ
A070
Cause:
No setpoints received from PROFIBUS-DP communication board.
Triggered by A702/A703/A704.
The telegram failure time set in P2040 has run out.
Remedy:
Check connection to communication partners and ensure valid
control word (see A702/A703/A704)
Summary of Contents for Micromaster Profibus
Page 1: ...0 520 67 5 352 86 2SWLRQDO RDUG 2SHUDWLQJ LQVWUXFWLRQV GLWLRQ 8VHU RFXPHQWDWLRQ ...
Page 2: ......
Page 8: ... GLWLRQ PROFIBUS Optional Board Operating instructions 8 6SE6400 5AK00 0BP0 ...
Page 10: ... GLWLRQ PROFIBUS Optional Board Operating instructions 10 6SE6400 5AK00 0BP0 ...
Page 60: ... SSHQGL GLWLRQ PROFIBUS Optional Board Operating instructions 60 6SE6400 5AK00 0BP0 ...
Page 62: ... ORVVDU GLWLRQ PROFIBUS Optional Board Operating instructions 62 6SE6400 5AK00 0BP0 ...
Page 64: ......
Page 65: ......