Page 4

Heated Enclosure – INSTRUCTION MANUAL 

7ML1998IFY01

mmmm

m

Inst

allat

ion

Installation

Mounting

Mounting Locations

Recommended

Mount enclosure at shoulder level, unless most interaction of the enclosed 
instrument is through a SCADA system

Ensure easy access for instrument hand programmer is provided 

Mounting surface is free from vibration

Avoid 

Proximity to high voltage/current runs, contacts, SCR or variable frequency motor 
speed controllers

Mounting Instructions

Mount the unit where there is sufficient room to swing lid open and have clear access to 
contents.

Maintenance

The Heated Enclosure requires no internal cleaning. For external cleaning, wipe with 
damp cloth.

Notes

• Installation must only be performed by qualified personnel, and in accordance 

with local governing regulations.

• This product is susceptible to electrostatic shock. Follow proper grounding 

procedures.

• The non-metallic enclosure does not provide grounding between conduit 

connections. Use grounding type bushings and jumpers.

• Installation information applies to Heated Enclosure only. Please refer to level 

instrument documentation for installation guidelines.

All field wiring must have insulation suitable for at least 250 V.

Heater Box.fm  Page 4  Wednesday, April 24, 2002  9:47 AM

Summary of Contents for Milltronics HydroRanger 200

Page 1: ...HEATED ENCLOSURE Instruction Manual April 2002 EATED ENCLOSURE ...

Page 2: ...on and in electronic version We encourage users to purchase authorized bound manuals or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc Siemens Milltronics Process Instruments Inc will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions While we have verified the contents of this manual for...

Page 3: ...door applications Designed to resist wet and dirty conditions it is particularly effective for condensation control The impact resistant enclosure eliminates dents weathers well and is highly resistant to corrosives acids alkalines and salts Enclosure Features hinge caps nonmetallic molded in hinges rounded corners non conductive eliminates electrical shock risk sufficient interior space for wirin...

Page 4: ...57 F closes at 7 C 45 F Vertical Enclosure Dimensions W 420 mm 16 5 H 370 mm 14 5 D 215 mm 8 46 Horizontal Enclosure Dimensions W 370 mm 14 5 H 420 mm 16 5 D 215 mm 8 46 Important All specifications are subject to change without notice Please ensure that any safety related information is confirmed with a qualified Siemens Milltronics representative Approval information applies to Heated Enclosure ...

Page 5: ... 2 IQ Radar 300 INSTRUCTION MANUAL Page 3 mmmmm Specifications Enclosure Cover clear poly carbonate Approvals NEMA 1 3 3S 4 4X 12 13 Listed per UL 50 enclosures for electrical equipment CSA certified JIC compliant ...

Page 6: ... sufficient room to swing lid open and have clear access to contents Maintenance The Heated Enclosure requires no internal cleaning For external cleaning wipe with damp cloth Notes Installation must only be performed by qualified personnel and in accordance with local governing regulations This product is susceptible to electrostatic shock Follow proper grounding procedures The non metallic enclos...

Page 7: ...ical Mounting Horizontal Mounting Orientation changes but enclosure dimensions are identical to vertical mount Note For ease of use mount with hinges at bottom so lid hangs open when unlatched 305mm 12 00 420mm 16 50 480mm 19 00 7 9mm DIA 0 312 TYP 4 PLACES 370mm 14 50 215mm 8 46 ...

Page 8: ...eration 2 Attach conduit using only approved suitable sized hubs for watertight operation Vertical Mounting Horizontal Mounting Important Select conduit hole locations carefully Place them where the wiring will not interfere with Heated Enclosure operations Notes Use conduit hubs certified approved as Type 4X Non metallic enclosure does not provide grounding between conduit connections Use groundi...

Page 9: ...s the disconnect switch must be in close proximity to the equipment and within easy reach of the operator Do not connect level monitor to enclosure terminals Important All safety and operating information in this manual apply to the Heated Enclosure only Consult instrument manual for safety and operating instructions COVER NOT SHOWN 115Vac 120VA L1 L1 L2 N L2 N thermostat Milltronics Level Monitor...

Page 10: ...izontal Mount L1 L1 L2 N L2 N 115Vac 120VA enclosure ground lug terminal terminal block strip heater thermostat Milltronics Level Monitor level monitor cable entry refer to individual product for power consumption Note do not wire level monitor to Heated Enclosure terminal ...

Page 11: ...7ML19981FY01 Heated Enclosure INSTRUCTION MANUAL Page 9 mmmmm Notes Notes ...

Page 12: ... 7ML19981FY01 Siemens Milltronics Process Instruments Inc 2002 Subject to change without prior notice Rev 1 0 ...

Reviews: