Page 6
Heated Enclosure – INSTRUCTION MANUAL
7ML1998IFY01
mmm
mm
Wiring
Conduit Entry
Conduit entry is required for Heated Enclosure power supply, level monitor power supply,
and for transducer and communications wiring.
1.
Drill the required entry holes. Make sure holes do not interfere with Heated Enclo-
sure operation.
2.
Attach conduit using only approved suitable sized hubs for watertight operation.
Vertical Mounting
Horizontal Mounting
Important: Select conduit hole locations carefully. Place them where
the wiring will not interfere with Heated Enclosure operations.
Notes:
• Use conduit hubs certified/approved as Type 4X
• Non-metallic enclosure does not provide grounding between conduit
connections. Use grounding type bushings and jumper wires.
hinges
Recommended Conduit Locations
hinges
Recommended Conduit Locations