2

Front Door

Backbox

Figure 2

Reinstalling the Front Door

Figure 3

Inserting the Filler Plates in the Front Door

MOUNTING PLATES

(MBR-MP and MBR-3MP)

Install the MBR-MP and MBR-3MP Mounting Plates,
which are shipped separately. Refer to the MBR-MP/
MBR-3MP Installation Instructions,
 P/N 315-094882.

WIRING

In compliance with UL-864, effective May 1, 1995,
all power limited fire protective signaling conduc-
tors must be separated a minimum of 1/4 inch from
all of the following items located within a control
panel:

• electric light
• power
• Class 1 or non-power limited fire protective

signaling conductors

To meet the above requirements, the following
guidelines must be observed when installing
modules and wiring to this control panel.

NOTE: If power-limited wiring is not used within

an MXL/MXLV enclosure, then the follow-
ing guidelines do not apply. In that case,
be sure to follow standard wiring practices.

FRONT DOOR

The front door is the main outer door for the
MLE-6 enclosure. The door is supplied
without filler plates for the three large
openings. To select the appropriate filler
plates for the three openings, follow the
information below.

• When visual indication of system

operation (LCD, LED, or printer) is
required,
 install clear panels, the MDL-1
lens, behind the appropriate door
openings.

• When visual indication of the system

operation is not required, install plain
blank panels, MDB-1s, behind the
appropriate door openings.

• When audio amplifiers such as the

EL-410C/D or ZAC-30 are used,
install the MDG-1 (MXL Door Venting
Grill) behind the appropriate door
openings.

• After determining which filler plates

are required, insert the appropriate
plates in the front door as shown in
Figure 3 using the hardware supplied.

Summary of Contents for MLE-6

Page 1: ... accessible NOTE When the backbox is mounted semi flush be sure that the position of the backbox permits the front door to swing fully open To install the MLE 6 backbox Refer to Figure 1 1 Slip the front door off the hinges of the box and put it to one side temporarily 2 Remove the knockouts in the backbox where field wiring is required 3 Hold the empty backbox against the wall at a height that pr...

Page 2: ...ng is not used within an MXL MXLV enclosure then the follow ing guidelines do not apply In that case be sure to follow standard wiring practices FRONT DOOR The front door is the main outer door for the MLE 6 enclosure The door is supplied without filler plates for the three large openings To select the appropriate filler plates for the three openings follow the information below When visual indica...

Page 3: ...Wiring Note Power limited circuits must use type FPLP FPLR or FPL cable per article 760 of the NEC Wiring to the following MXL MXLV module terminations See Table 2 is considered power limited and must enter the enclosure through knockouts dedicated to power limited wiring Wiring between these knockouts and the module terminations must be in the shortest route and most not overlap any other wiring ...

Page 4: ...urce WIRING IN THE REMOTE ENCLOSURE Non Power Limited Wiring The following wiring is considered non power limited from the MPS 6 W or MPS 12 W from the batteries to the PSR 1 To maintain the required 1 4 inch separation from other wiring these wires must be routed and held in place by a separate wire support This support is positioned on the left side wall of the enclosure To provide the separatio...

Reviews: