7.3.8 Coil Loop Data (1-bit)
Controller [ODC]
Code
R/W
Description
Range
Coil(MB)
C/P (LIL)
L#A
R/W
1-Auto 0-Manual
1/0
00296+48(#-1)
n+3/1(0)
L#L R/W 1-Local
1/0
00297+48(#-1) n+3/1(1)
L#SS
R
1-AM block in STANDBY
1/0
00298+48(#-1)
n+3/1(2)
L#E R/W 1-External
Set
1/0
00299+48(#-1) n+3/1(3)
L#CN R/W 1-Console
1/0
00300+48(#-1) n+3/1(4)
L#CM R/W 1-Computer
1/0
00301+48(#-1) n+3/1(5)
L#RS R/W 1-Ramping
Setpoint 1.0
00302+48(#-1)
n+3/1(6)
L#OR R
1-Override
1/0
00303+48(#-1) n+3/1(7)
L#EM R
1-Emergency
Manual
1/0
00304+48(#-1) n+3/1(8)
L#CH R
1-Configuration
Hold
1/0
00305+48(#-1) n+3/1(9)
L#HL
R
1-HI Setpoint Limit
1/0
00306+48(#-1)
n+3/1(10)
L#LL
R
1-LO Setpoint Limit
1/0
00307+48(#-1)
n+3/1(11)
L#OS
R/W
1-Alarms - Out of Service
1/0
00308+48(#-1)
n+3/1(12)
L#U1S R
1-U1 Status Active
1/0
00309+48(#-1)
n+3/1(13)
L#U2S R
1-U2 Status Active
1/0
00310+48(#-1)
n+3/1(14)
L#AT R/W 1-Autotune
1/0
00311+48(#-1) n+3/1(15)
L#A1
R
1-Alarm 1 is Active
1/0
00312+48(#-1)
n+4/1(0)
L#N1
R/W
1-Alarm 1 is Not Acknowledged 1/0 00313+48(#-1)
n+4/1(1)
L#E1
R/W
1-Alarm 1 is Enabled
1/0
00314+48(#-1)
n+4/1(2)
L#A2
R
1-Alarm 2 is Active
1/0
00315+48(#-1)
n+4/1(3)
L#N2
R/W
1-Alarm 2 is Not Acknowledged 1/0 00316+48(#-1)
n+4/1(4)
L#E2
R/W
1-Alarm 2 is Enabled
1/0
00317+48(#-1)
n+4/1(5)
L#A3
R
1-Alarm 3 is Active
1/0
0318+48(#-1)
n+4/1(6)
L#N3
R/W
1-Alarm 3 is Not Acknowledged 1/0 00319+48(#-1)
n+4/1(7)
L#E3
R/W
1-Alarm 3 is Enabled
1/0
00320+48(#-1)
n+4/1(8)
L#A4
R
1-Alarm 4 is Active
1/0
00321+48(#-1)
n+4/1(9)
L#N4
R/W
1-Alarm 4 is Not Acknowledged 1/0 00322+48(#-1)
n+4/1(10)
L#E4
R/W
1-Alarm 4 is Enabled
1/0
00323+48(#-1)
n+4/1(11)
L#OS2 R/W
1-Alarms - Out of Service
1/0
00324+48(#-1)
n+4/1(12)
L#CC
R
1-Configuration has Changed 1/0
00325+48(#-1)
n+4/1(13)
L#NA
R/W
1-Unacknowledged Loop Event
1/0
00326+48(#-1)
n+4/1(14)
L#AE
R
1-Active Loop Event
1/0
00327+48(#-1)
n+4/1(15)
L#NSS R/W
1-Not Ack’d STANDBY
(V1.3)
1/0 00328+48(#-1)
n+4/10(0)
L#NOR R/W
1-Not Ack’d Override
(V1.3)
1/0 00329+48(#-1)
n+4/10(1)
L#NEM R/W
1-Not Ack’d Emergency Man
(V1.3)
1/0
00330+48(#-1)
n+4/10(2)
L#NHL R/W
1-Not Ack’d HI Setpoint Limit
(V1.3)
1/0
00331+48(#-1)
n+4/10(3)
L#NLL R/W
1-Not Ack’d LO Setpoint Limit
(V1.3)
1/0
00332+48(#-1)
n+4/10(4)
L#NU1 R/W
1-Not Ack’d U1 Status
(V1.3)
1/0 00333+48(#-1)
n+4/10(5)
L#NU2 R/W
1-Not Ack’d U2 Status
(V1.3)
1/0 00334+48(#-1)
n+4/10(6)
L#NW1 R/W
1-Not Ack’d W1 Status
(V1.3)
1/0 00335+48(#-1)
n+4/10(7)
L#NW2 R/W
1-Not Ack’d W2 Status
(V1.3)
1/0 00336+48(#-1)
n+4/10(8)
L#NW3 R/W
1-Not Ack’d W3 Status
(V1.3)
1/0 00337+48(#-1)
n+4/10(9)
L#NE1 R/W
1-Not Ack’d E1 Status
(V1.3)
1/0 00338+48(#-1)
n+4/10(10)
L#NE2 R/W
1-Not Ack’d E2 Status
(V1.3)
1/0 00339+48(#-1)
n+4/10(11)
L#NE3 R/W
1-Not Ack’d E3 Status
(V1.3)
1/0 00340+48(#-1)
n+4/10(12)
L#XAT W
1-Transfer Autotune Parameters
(V1.3)
1/0 00341+48(#-1)
n+4/10(13)
L#PB1C R/W
PB1SW Input MD (*)
(V1.3)
1/0 00342+48(#-1)
n+4/10(14)
L#PB2C R/W
PB2SW Input MD (*)
(V1.3)
1/0 00343+48(#-1)
n+4/10(15)
* These bits indicate the status of the switch input MD. A write of a “1” will have the same effect as pressing and releasing the
button on the faceplate. If the action of the switch is sustained the switch will change position. If the action is momentary
the switch will close for one scan cycle.
StockCheck.com
Summary of Contents for Moore 353
Page 2: ...S t o c k C h e c k c o m ...
Page 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Page 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Page 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Page 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Page 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Page 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Page 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Page 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Page 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Page 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...