Data Mapping
UM353-1
March
2003
7-46
7.3.13 Configuration Data Sequencer Loop
The Modbus registers or LIL parameters on this page refer to configuration parameters of function blocks within a
specific loop previously defined by Modbus parameter MSLCP (40048) or LIL parameter LSLCP (7/1). For
example, to read or write the Step 1 Group 0 Input Mask for the PRSEQ block that is in a loop with a Modbus Index
of 3, write a 3 to 40048, then read or write to register 410001.
Sequencer (MASK Configurations)
Code
`
R/W
Description
Range
Register (MB)
C/P (LIL)
S001G0I
R/W
Step 1 Group 0 Input Mask
$0000-$FFFF
410001
1/154
S001G0O
R/W
Step 1 Group 0 Output Mask
$0000-$FFFF
410002
1/170
S001G1I
R/W
Step 1 Group 1 Input Mask
$0000-$FFFF
410003
1/155
S001G1O
R/W
Step 1 Group 1 Output Mask
$0000-$FFFF
410004
1/171
S001G2I
R/W
Step 1 Group 2 Input Mask
$0000-$FFFF
410005
1/156
S001G2O
R/W
Step 1 Group 2 Output Mask
$0000-$FFFF
410006
1/172
S001G3I
R/W
Step 1 Group 3 Input Mask
$0000-$FFFF
410007
1/157
S001G3O
R/W
Step 1 Group 3 Output Mask
$0000-$FFFF
410008
1/173
.........................................................................................................................................................................................
S250GEI
R/W
Step 250 Group E Input Mask
$0000-$FFFF
417997
250/168
S250GEO
R/W
Step 250 Group E Output Mask
$0000-$FFFF
417998
250/184
S250GFI
R/W
Step 250 Group F Input Mask
$0000-$FFFF
417999
250/169
S250GFO
R/W
Step 250 Group F Output Mask
$0000-$FFFF
418000
250/185
Real TimeTrip Block Configurations
Code
R/W
Description
Range
Register (MB)
C/P (LIL)
RTT01Y
R/W
Year
1999-
419001
1/100 V 2.0
RTT01M
R/W
Month
1-12
419002
1/101 V 2.0
RTT01D
R/W
Day
1-31
419003
1/102 V 2.0
RTT01HR
R/W
Hour
0-23
419004
1/103 V 2.0
RTT01MN
R/W
Minute
0-59
419005
1/104 V 2.0
RTT01SC
R/W
Second
0-59
419006
1/105 V 2.0
RTT01DA
R/W
Day
0000 0000 0SMT WTFS
419007
1/106 V 2.0
RTT02Y
R/W
Year
1999-
419008
2/100 V 2.0
RTT02M
R/W
Month
1-12
419009
2/101 V 2.0
RTT02D
R/W
Day
1-31
419010
2/102 V 2.0
RTT02HR
R/W
Hour
0-23
419011
2/103 V 2.0
RTT02MN
R/W
Minute
0-59
419012
2/104 V 2.0
RTT02SC
R/W
Second
0-59
419013
2/105 V 2.0
RTT02DA
R/W
Day
0000 0000 0SMT WTFS
419014
2/106 V 2.0
RTT03Y
R/W
Year
1999-
419015
3/100 V 2.0
RTT03M
R/W
Month
1-12
419016
3/101 V 2.0
RTT03D
R/W
Day
1-31
419017
3/102 V 2.0
RTT03HR
R/W
Hour
0-23
419018
3/103 V 2.0
RTT03MN
R/W
Minute
0-59
419019
3/104 V 2.0
RTT03SC
R/W
Second
0-59
419020
3/105 V 2.0
RTT03DA
R/W
Day
0000 0000 0SMT WTFS
419021
3/106 V 2.0
StockCheck.com
Summary of Contents for Moore 353
Page 2: ...S t o c k C h e c k c o m ...
Page 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Page 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Page 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Page 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Page 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Page 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Page 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Page 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Page 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Page 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...