Installation
UM353-1
March
2003
8-22
8.4.10 LonWorks Wiring
Figure 8-23 shows typical LonWorks network wiring to the Moore 353. The network termination resistor is
supplied in the installation kit. Connections to remote devices are described in each device User’s Manual, supplied
with the devices. See Section 8.4.2 for wiring guidelines.
25
Remote Devices
Controller Terminals
26
C
ontr
ol
ler
C
irc
ui
tr
y
IOA
IOB
LonWorks
Board
node 1
node n
= 22 Gauge (AWG) Twisted Pair Wire
X03143S2
G
P
P
P
52.3 Network
Termination Resistor
Ω
FIGURE 8-23 LonWorks Network Wiring
8.4.11 Modbus Wiring
This section describes the wiring needed to connect a host device to a Moore 353’s Modbus network interface.
When connected, the host can read data from and write data to a Moore 353 in a command/response format.
Most host devices communicate using RS232 while the Modbus network interface is RS485. As shown in Figure 8-
24, a 2-wire RS485 to RS232 converter is installed to perform the protocol conversion and adapt the connection
hardware. A shielded RS232 cable with either DB9 or DB25 connectors is installed between the host device and
the converter. An RS485 shielded, twisted-pair cable connects the converter to a Moore 353. Up to 32 Moore 353s
can be connected since RS485 is a multi-drop network.
Shown below are the jumper locations and identifiers for the Entrelec® Isolated Converter shown in Figure 8-24.
Rt (INT1)
R (INT2)
E (INT3)
For access to jumpers
carefully remove the side
of the module that has the
jumper label.
Entrelec ILPH 084.233.11 Isolated Converter
RS485 link on
one pair
A
G
00336
a
120
Ω
8.4.12 Ethernet Wiring
A sample architecture and a brief description are
presented in the Introduction section of this manual. An
RJ-45 Ethernet connector is located on the back of the
case and the optional Ethernet board is mounted on the
MPU Controller board. Ethernet cables external to the
controller must be rated Category 5 or better. Shielded
cable is highly recommended outside the panel or
cabinet, as shown at right.
Moore 353
with Ethernet
Moore 353
with Ethernet
Moore 353
with Ethernet
Hub or
Switch
Industrial Ethernet
Shielded Cable
Siemens Industrial
Ethernet Fast Connect
PN 66K1901-1FC00-0AA0
MG
0040
2a
Panel or Cabinet
StockCheck.com
Summary of Contents for Moore 353
Page 2: ...S t o c k C h e c k c o m ...
Page 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Page 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Page 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Page 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Page 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Page 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Page 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Page 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Page 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Page 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...