Mounting
4.7 Connecting the motor
BA 2320
Operating Instructions, 02/2015, 70000004023775
35
4.7.8
Tightening torque for bolts in electrical connections
Terminal board connection
Please observe the following tightening torques for bolts on the terminal box and grounding
conductors.
Table 4- 5
Tightening torque for terminal board connection
Thread size
Tightening torque
Thread size
Tightening torque
min.
max.
min.
max.
[Nm]
[Nm]
[Nm]
[Nm]
M4
0.8
1.2
M10
9
13
M5
1.8
2.5
M12
14
20
M6
2.7
4
M16
27
40
M8
5.5
8
Type of conductor connection
Table 4- 6
Conductor cross-section
When connecting using a DIN cable lug: Angle the cable lug downwards as described in DIN 46 234
... 25 mm
2
Connection of an individual conductor with terminal clamp
... 10 mm
2
Summary of Contents for MOTOX BA 2320
Page 1: ......
Page 2: ......
Page 42: ...Mounting 4 7 Connecting the motor BA 2320 42 Operating Instructions 02 2015 70000004023775 ...
Page 48: ...Operation BA 2320 48 Operating Instructions 02 2015 70000004023775 ...
Page 64: ...Disposal BA 2320 64 Operating Instructions 02 2015 70000004023775 ...
Page 80: ......
Page 83: ......
Page 84: ......